20 April 2018 in IEEE Sensors Journal
Measuring the current in high-voltage direct current (HVDC) systems is always regarded as a challenging task. For transmission systems, DC current transformers or sensors are only available in substations and converter stations. In order to provide more flexibility and convenience, this paper proposes a contactless DC current sensor, which can be easily placed on-site in the environment of HVDC overhead transmission lines. The proposed method significantly improves the convenience and safety of the HVDC current measurement. Using a magnetic-field sensor array, the proposed current algorithm can optimally calculate the overhead-line currents with partially known overhead-line geometry. The simulation results in this paper demonstrate that the proposed method can accurately calculate the HVDC current. Moreover, the proposed method is validated by a reduced-scale HVDC overhead transmission line.
16 June 2022 in IEEE Transactions on Instrumentation and Measurement
To improve the efficiency of power transmission, high-voltage direct current (HVdc) transmission systems are crucial power-related development in many countries. This study proposes a contactless dc current measurement method suitable for on-site measurements of HVdc overhead lines. In this method, a vertical magnetic field (MF) sensor array (three layers and one three-axis MF sensor installed in each layer) is designed to measure the spatial MFs on the ground. With the spatial MFs measured by the sensor array and the overhead-line specifications obtained from utilities, the core current algorithm of the proposed method can accurately calculate the current values. In addition, we design a magnetic shielding mechanism to correct a dc offset that is inevitably output from each MF sensor. The dc offset includes the quiescent voltage of the self-circuit of the MF sensor and the output voltage of the MF sensor caused by the earth’s MF. Thus, this mechanism can effectively solve the problem in which the dc offset is misjudged as an MF formed by the measured current. The simulation results indicate that under arbitrary vertical sensor array placements, the core convergence condition (geomagnetic invariance) of the proposed current algorithm can improve the algorithm convergence. Finally, the experimental results verify the feasibility of the proposed method for the measurement of overhead-line current. Without conductor sags, all the current errors are less than 2% in both the 500- and 800-kV overhead-line scenarios. Moreover, even with serious conductor sags, all the current errors are still within 9%.
21 December 2017 in IEEE Sensors Journal
The temperature drift of the current sensor with an air gap limits its measurement accuracy, so a ferromagnetic design is presented to improve the temperature characteristics of the current sensor by an air-gapped magnetic field intensity self-compensation. In this study, the magnetostriction and thermal expansion is introduced into a hysteresis model within the temperature range from 258 K to 358 K, and the relationship between the permeability and the air-gapped length of amorphous alloy is analyzed. The results show that the air-gapped length increases as the temperature increases, resulting in the air-gapped magnetic field intensity weakened. Moreover, the permeability of amorphous alloy increases as the temperature increases, resulting in the air-gapped magnetic field intensity strengthened. Hence, the air-gapped magnetic field intensity can be self-compensated with the amorphous alloy. The effectiveness of the design is verified experimentally with 1-10mm air-gapped amorphous cores. In addition, in order to analyze the air-gapped magnetic field intensity changes more accurately, a new hysteresis modeling method is proposed, which can overcome the disadvantages of J-A model for the minor hysteresis curve simulations and Preisach model for the major hysteresis curve simulations.