When passing through complex terrain, overhead bare wires may come into contact with tree branches, residential buildings, masts, or other obstacles, potentially leading to phase-to-phase or single phase-to-ground short circuits. To address the electric field distortion at the insulation-bare conductor junction in overhead hybrid wires, this study proposes a novel functionally graded insulation (FGI) structure design coupled with nonlinear conductivity materials for electric field regulation. An axisymmetric finite element model of the proposed structure at a 220 kV AC line junction was established. Comparative simulations of scenarios with no insulation enhancement and with a neat silicone rubber structure verified its preliminary field-regulating effectiveness. To further enhance adaptive field control, five different SiC/silicone rubber (SiC/SR) composites were introduced into the reinforced insulation layer. Simulations were conducted to analyze the influence of filler content and particle size on the field-regulation characteristics. Results show that the 10% vol-1.5 μm SiC/SR composite demonstrates9 optimal field homogenization, notably reducing the maximum junction field by 27.96% and the cone surface field by 65.02%, while optimizing the non-uniformity coefficient to 1.22. This synergistic design effectively suppresses field distortion, providing a theoretical and practical basis for insulating overhead hybrid transmission lines.