Hao Yu

Hao Yu

Auto-generated profile, based on publicly available information

Hao Yu

State Grid Heilongjiang Electric Power Co., Ltd. Electric Power Research Institute

Research Focus & Metrics

Academic Career Length

7Years (2020-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
1 May 2020 in IOP Conference Series: Earth and Environmental Science
Verified
Conference Paper
Open access
DZDewen Zhang
Dewen Zhang
XHXiaoxu Hu
Xiaoxu Hu
HZHongda Zhang
Hongda Zhang
HYHao Yu
Hao Yu
YSYubo Shen
Yubo Shen
Ferroresonance is an important factor affecting the security and stability operation of Gas Insulated Switchgear (GIS) substation. The nonlinearity of excitation characteristic of inductance elements with iron cores is the fundamental cause for exciting ferroresonance. A 500kV GIS substation is taken into account in this paper, a variety of operating conditions which may excite ferroresonance during the commissioning process are analyzed by a numerical simulation method. The comparison with actual commissioning results shows that ferroresonance will be excited by opening circuit breakers to switch off no-load buses during the commissioning process. For single-phase electromagnetic potential transformer (PT), ferroresonance can be effectively suppressed by connecting damping resistance in parallel with residual winding temporarily.