This study presents a comparison of two developed intelligent systems that carries out, in an integrated manner, failure diagnosis on electric power distribution feeders. These procedures aim to identify and classify critical situations, as high‐impedance faults, which can potentially damage the system components and cause power supply interruptions to consumers. The intelligent systems combine the wavelet transform, Dempster–Shafer evidence theory, voting scheme, fuzzy inference system and artificial neural networks. Results show the efficiency, reliability, and robustness of the proposed methodology, allowing its real‐time application.
5 November 2012 in IET Generation, Transmission & Distribution
The present study proposes a methodology for the automatic diagnosis of short-circuit faults in distribution systems using modern techniques for signal analysis and artificial intelligence. This support tool for decision making accelerates the restoration process, providing greater security, reliability and profitability to utilities. The fault detection procedure is performed using statistical and direct analyses of the current waveforms in the wavelet domain. Current and voltage signal features are extracted using discrete wavelet transform, multi-resolution analysis and energy concept. These behavioural indices correspond to the input vectors of three parallel sets of fuzzy ARTMAP neural networks. The network outcomes are integrated by the Dempster–Shafer theory, giving quantitative information about the diagnosis and its reliability. Tests were carried out using a practical distribution feeder from a Brazilian electric utility, and the results show that the method is efficient with a high level of confidence.
1 February 2020 in Electric Power Systems Research
This paper presents a tool for the detection and classification of short-circuits in electric power distribution systems, which is based on the combined use of multi-resolution analysis and Fuzzy-ARTMAP neural network. The multiresolution analysis allows the identification of singularities in the waveforms and the ART family network guarantees to the classifier the ability to continuously learn without losing the previously acquired knowledge. The entire diagnosis procedure is performed in a single step, reducing the computational effort. The efficiency of the system is verified by a direct accuracy analysis, and by a comparison between the Fuzzy-ARTMAP and the EuclideanARTMAP. Results show that the system is efficient and robust, being able to detect and classify 100% of the electrical faults considering the test that were performed.
14 September 2015 in Electric Power Components and Systems
This article presents a method to detect and classify voltage disturbances in electric power distribution systems using a modified Euclidean ARTMAP neural network with continuous training. This decision-making tool accelerates the procedures to restore the normal operation conditions providing security, reliability, and profits to utilities. Furthermore, it allows the diagnosis system to adapt to changes from the constant evolution of the electric system. The voltage signals features or signatures are extracted using discrete wavelet transform, multiresolution analysis, and the energy concept. Results show that the proposed methodology is robust and efficient, providing a fast diagnosis process. The data set used to validate the proposal is obtained by simulations in a real distribution system using ATP software.