Electrical distribution system reconfiguration is frequently addressed as a multi-objective problem, typically taking into account the system losses together with other objectives, among which reliability indicators are widely used. In the multi-objective context, Pareto front analysis enables the operator handling conflicting and even non-commensurable objectives without needing the use of additional hypotheses or weights. This paper provides advances on the application of Pareto front analysis to multi-objective distribution network reconfiguration. Starting from previous results in which genetic algorithms were effectively adopted to find the best-known Pareto front, a version of the multi-objective binary particle swarm optimization (MOBPSO) customized for distribution network reconfiguration has been developed by exploiting the internal ranking of the solutions (based on a multi-criteria decision making method in the selection of the local best) and the network topology. Furthermore, the Pareto front mismatch metric (already used by the authors to compare different methods for small networks for which the complete Pareto front can be calculated) has been generalized to be used with large systems for which only the best-known Pareto front is found. Applications to a test network and to a real urban distribution network are discussed, showing the consistent superiority of the customized MOBPSO version with respect to the application of genetic algorithms and of a more classical version of the particle swarm optimization method.
In this paper one and two shells magneto static cylindrical shields are considered. Using the interface conditions at the discontinuity surfaces between the media, algebraic systems of equations have been obtained. Solution of the systems offers the value of the magneto static field inside the shields. Structures of the system's matrices were analyzed and their sparsity patterns was visualized. 3D Finite element simulations of shields with different lengths were performed and comparisons with analytical results were done. Good agreement, among the shields efficiencies for different lengths and the analytical value, were obtained.
The purpose of research presented in this paper is the obtaining of magnetic sensors. These sensors were made with the PLD method (Pulsed Laser Deposition) by deposition on substrates of Silicon Oxide. Experimental tests were performed with VSM (Vibrating Sample Magnetometer). The GMR effect (Giant Magneto-Resistance) was highlighted in this thin multilayer of CU/CO and the use of these as field magnetic sensors.