Jong-Hyuk Lee

Jong-Hyuk Lee

Auto-generated profile, based on publicly available information

Jong-Hyuk Lee

HVDC Production Team, LSIS Co., Ltd , Busan , 46739 , Republic of Korea

Research Focus & Metrics

Academic Career Length

18Years (2009-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
2 November 2017 in Energies
Verified
Journal Article
Open access
PDF file
GWGUOMING WANG
GUOMING WANG
GKGYUNG-SUK KIL
GYUNG-SUK KIL
HJHong-Keun Ji
Hong-Keun Ji
JLJong-Hyuk Lee
Jong-Hyuk Lee
With the increasing demand for precise condition monitoring and diagnosis of gas-insulated switchgears (GISs), it has become a challenge to improve the detection sensitivity of partial discharge (PD) induced in the GIS spacer. This paper deals with the elimination of the capacitive component from the phase-resolved partial discharge (PRPD) signal generated in GIS spacers based on discrete wavelet transform (WT). Three types of typical insulation defects were simulated using PD cells. The single PD pulses were detected and were further used to determine the optimal mother wavelet. As a result, the bior6.8 was selected to decompose the PD signal into 8 levels and the signal energy at each level was calculated. The decomposed components related with capacitive disturbance were discarded, whereas those associated with PD were de-noised by a threshold and a thresholding function. Finally, the PRPD signals were reconstructed using the de-noised components.

1 September 2018 in Journal of Electrical Engineering
Verified
Journal Article
Open access
PDF file
GWGuoming Wang
Guoming Wang
WKWoo-Hyun Kim
Woo-Hyun Kim
JLJong-Hyuk Lee
Jong-Hyuk Lee
GKGYUNG-SUK KIL
GYUNG-SUK KIL
With the growing demand for application of metal-oxide varistor (MOV) in low-voltage electronic circuits for overvoltage protection, it is necessary to ensure its performance to avoid the short-circuit and the line-to-ground fault during operation. In this paper, a precise leakage current analyzer was developed to detect the total leakage current and third harmonic component of MOV for its condition monitoring. The voltage- and temperature-dependent measuring uncertainties were compensated using the multipliers. In addition, the deterioration characteristics of the MOV and the newly developed thermally protected metal-oxide varistor (TMOV) were investigated in the accelerated aging test. From the experimental results, the MOV deteriorated much faster under the lightning current impulse synchronized with power-frequency voltage. The thermally activated fuse of TMOV exploded under two types of impulses, which indicated that the TMOV is much more vulnerable and that it is difficult to diagnose the condition of energized TMOV in advance.

24 October 2017 in Preprints.org
Verified
Preprint
Open access
PDF file
GWGUOMING WANG
GUOMING WANG
GKGYUNG-SUK KIL
GYUNG-SUK KIL
HJHong-Keun Ji
Hong-Keun Ji
JLJong-Hyuk Lee
Jong-Hyuk Lee
With the increasing demand for precise condition monitoring and diagnosis of gas-insulated switchgears (GIS), it has become a challenge to improve the detection sensitivity of partial discharge (PD) induced in the GIS spacer. This paper deals with the elimination of the capacitive component from the phase resolved partial discharge (PRPD) signal generated in GIS spacer based on the discrete wavelet transform. Three types of typical insulation defects were simulated using PD cells. The single PD pulses were detected and were further used to determine the optimal mother wavelet. As a result, the bior6.8 was selected to decompose the PD signal into 8 levels and the signal energy at each level was calculated. The decomposed components related with capacitive disturbance were discarded whereas those associated with PD were de-noised by a threshold and a thresholding function. Finally, the PRPD signals were reconstructed using the de-noised components.

1 January 2009
Verified
Conference Paper
Closed access
JLJong-Hyuk Lee
Jong-Hyuk Lee
JMJi-Hoon Ma
Ji-Hoon Ma
GKGyung-Suk Kil
Gyung-Suk Kil
In recent years, the companies of electric power equipments for MV and HV class trend to develop the ecofriendly insulated switchgear which replaces existent SF6 gas insulated switchgear due to environmental problems such as global warming and so on. This paper makes reference to the newly developed solid insulated switchgear (SIS) which uses the ecofriendly material such as epoxy for insulation. The insulation material of the Solid Insulated switchgear (SIS) is composed of an epoxy, vacuum and air. The Solid Insulated Switchgear (SIS) is a state of the art product. In the product(SIS), there are a lot of advantages such as advanced reliability, safety, economical efficiency, maintenance free, reduction of installation area and the protection of environment. This paper is intended to introduce characteristics for a newly developed Solid Insulated Switchgear (SIS). (4 pages)