1 January 2020 in IET Science, Measurement & Technology
This study presents a dynamic arc model of a polluted insulator based on the formulation of the Obenaus model and the Hampton criterion for discharge propagation. An experiment was conducted on a practical glass insulator installed in the Algerian network for the purpose of measuring the flashover voltage and estimating the arc parameters ( A and N ) using a genetic optimisation algorithm. The parameters used in the dynamic model were the arc current, arc length, and arc resistance calculated using MATLAB. Moreover, an attempt was made with finite element software to calculate the voltage and electric‐field throughout the insulator surface with and without the presence of contaminants. Finally, the obtained simulation and experimental results showed high performances under operational conditions and respect IEC 60060‐1 standard recommendations.
23 April 2024 in Diagnostyka
In this work, a study on a cap and pin insulator (1512L) is proposed to evaluate the distribution of the electric field and the potential along the insulator under different conditions. A computational and experimental study for the examination of a real insulators model is assessed. Tests on...
10 September 2024 in PRZEGLĄD ELEKTROTECHNICZNY
Insulators with High voltage are the key components in energy transmission systems wich may be affected by pollution. In this paper, the performance of a cap and pin insulator is investigated with the objective of predicting the propagation of an AC surface arc on contaminated insulators in the presence of a non- uniform electric field. To assess the performance of the insulator, the electric field simulation is carried out by using the finite element method. Research results show that non-uniform contamination had the worst electric field profile. This work can provide a useful tool for the design and maintenance of cap and pin insulators.