5 January 2012 in IEEE Transactions on Power Systems
In this paper, a steady-state multi-terminal voltage source converter high voltage direct current (VSC MTDC) model is introduced. The proposed approach is extended to include multiple AC and DC grids with arbitrary topologies. The DC grids can thereby interconnect arbitrary buses in one or more non-synchronized AC systems. The converter equations are derived in their most general format and correctly define all set-points with respect to the system bus instead of the converter or filter bus, which is often done to simplify calculations. The paper introduces a mathematical model to include the converter limits and discusses how the equations change when a transformerless operation is considered or when the converter filter is omitted. An AC/VSC MTDC power flow is implemented using MATPOWER to show the validity of the generalized power flow model.
17 February 2010 in IEEE Transactions on Power Systems
In this paper, a new general voltage source converter high voltage direct current (VSC MTDC) model is derived mathematically. The full system model consists of the converter and its controllers, DC circuit equations, and coupling equations. The main contribution of the new model is its valid for every possible topology of the DC circuit. Practical implementation of the model in power system stability software is discussed in detail. The generalized DC equations can all be expressed in terms of matrices that are byproducts of the construction of the DC bus admittance matrix. Initialization, switching actions resulting in different topologies and simulation of the loss of DC lines amount to a simple calculation or recalculation of the DC bus admittance matrix. The model is implemented in Matlab. Examples on a two- and six-terminal system show that the new model is indeed capable of accurately simulating VSC MTDC systems with arbitrary topology.
10 April 2015 in IEEE Transactions on Power Delivery
This paper deals with nonunit protection of HVDC grids by proposing a set of parameters that characterizes the open protection zones together with an efficient method to determine the thresholds on these parameters. Selective HVDC grid protection schemes must detect and discriminate faults within the first milliseconds of the fault transient and consequently differ considerably from existing ac protection schemes. Due to the accompanying speed requirement, primary protection is expected to be based on open protection zones as communication delay impedes fast operation. In this paper, the principles of the nonunit protection scheme are developed based on reflection of a traveling wave at an inductive termination. Next, the method to obtain the protection scheme thresholds is elaborated. The method accurately calculates the thresholds for HVDC grids with an arbitrary topology. A sensitivity analysis of these thresholds toward grid and fault parameters demonstrates the applicability of the proposed protection scheme in cable-based HVDC grids with inductive cable termination. The results obtained with the reduced grid model are validated by comparison against simulations using a detailed model implemented in PSCAD.
5 September 2013 in IEEE Transactions on Power Systems
This paper discusses the extension of electromechanical stability models of voltage source converter high voltage direct current (VSC HVDC) to multi-terminal (MTDC) systems. The paper introduces a control model with a cascaded DC voltage control at every converter that allows a two-terminal VSC HVDC system to cope with converter outages. When extended to an MTDC system, the model naturally evolves into a master-slave set-up with converters taking over the DC voltage control in case the DC voltage controlling converter fails. It is shown that the model can be used to include a voltage droop control to share the power imbalance after a contingency in the DC system amongst the converters in the system. Finally, the paper discusses two possible model reductions, in line with the assumptions made in transient stability modeling. The control algorithms and VSC HVDC systems have been implemented using both MatDyn, an open source MATLAB transient stability program, as well as the commercial power system simulation package EUROSTAG.
20 August 2013 in IEEE Transactions on Power Systems
This paper analyzes the influence of the converter droop settings and the dc grid network topology on the power sharing in a dc grid based on voltage source converter high voltage direct current technology. The paper presents an analytical tool to study the effect of the droop control settings on the steady-state voltage deviations and power sharing after a converter outage, thereby accounting for dc grid behavior. Furthermore, an optimization algorithm is developed, taking into account two conflicting optimization criteria. The simulation results show that, when selecting appropriate values for the converter gains, a tradeoff has to be made between the power sharing and the maximum allowable dc voltage deviation after an outage.
6 October 2009 in IEEE Transactions on Industrial Electronics
In this paper, a prediction scheme is presented to diminish both the torque and flux ripples in a direct torque control (DTC) induction motor drive. In a discrete implementation of the classical DTC scheme, the time delay associated with data processing results in additional torque and flux ripples. This part of the ripples can amount to a significant fraction of the overall ripple if the hysteresis bands are comparable to the maximum torque and flux variations in one sampling interval. This paper presents a prediction scheme with low computational complexity and low parameter sensitivity, both comparable to the standard DTC scheme. The prediction scheme can easily be extended to compensate for multiple time delays when the sampling frequency is raised but the computation time remains unchanged. Experimental results show the diminishing effect of the prediction scheme on the torque and flux ripples.