Renewable energy units are required to have reliable fault ride-through capability to prevent large-scale disconnection of renewable energy plants due to grid faults. Since synchronous generators have better voltage and current resistance capabilities, one of the advantages of renewable energy connected to the grid through the motor-generator Pair (MGP) system is the isolation of grid faults, which is totally different from existing fault ride-through methods. First, the structure and mathematical model of the MGP system are introduced in this paper. Then, a novel control method for the MGP system based on DC link voltage feedback is given, which is very important for fault ride-through in the control power balance on both sides of the DC bus. The isolation mechanism, damping and reactive power support functions of the MGP system on grid faults are analyzed by means of the rotor motion equation and phasor diagram of synchronous machine. A 5-kW MGP simulation and experimental platforms are built to verify the isolation and protection effects of the MGP system on a renewable energy generation system during the transient processes of grid voltage sag, overvoltage and multiple voltage sags. The results demonstrate that the MGP system can isolate grid faults on the generator side, while the oscillation amplitude on the motor side is much smaller, and the generator can provide strong reactive power support to the grid during three grid faults.
With the increase of renewable energy in power system, the usage of a large number of converters brings safety and stability issues to power system, including lack of reliable inertia response, insufficient abilities for supporting current, voltage and frequency and lack of reliable damping to restrain oscillation. To solve these instability issues, the synchronous motor-generator pair (MGP) is proposed as a new method of grid-connection. Firstly, the main structure and application scene of MGP are analyzed. Secondly, the classical model for the MGP small signal stability is derived. Theoretical deduction proves that the MGP can provide more damping than a single generator with the same mass block. Then, 5kW MGP experimental system is built. The calculation parameters of the small signal model for the experimental system are determined by fitting experimental data repeatedly. On the basis, the calculated and measured frequency responses are compared under the same disturbance. The agreements between calculations and measurements show that the MGP small signal model can reflect damping and inertia level of MGP system. Finally, same disturbance experiment is carried out on a single-generator experimental system with the same mass block. The frequency response curves of the two modes under the same disturbance show that the MGP is more conducive to system stability.