In this paper, based on the data of the Ribnica accumulation (Serbia), and the required quality of raw and treated water, an optimal solution for improving and optimization of the technology of water purification to drinking quality at a water treatment plant (WTP) in Zlatibor, Serbia, was proposed to ensure maximum efficiency and flexibility in system operation. Analysis of water quality has shown that after the treatment at the plant, all parameters were within the respective maximum available concentrations (MAC) stipulated by the Rulebook on the hygienic suitability of potable water of the Republic of Serbia, except for the nickel content. The paper presents the results of the nickel removal using multiple laboratory tests as well as at the WTP to achieve the best procedure for water treatment. In accordance with the results obtained the water quality problem in terms of the nickel removal was solved and the required effects are obtained (nickel content below the MAC, i.e. <0.02 mg dm-3)
The paper presents results from the first year of continuous operation of the upgraded Zrenjanin drinking water treatment plant. Process stability and treatment performance for groundwater from the "Mihajlovački drum" wellfield were evaluated, with emphasis on colour, iron, natural organic matter and arsenic. Typical reductions were approximately 98% for colour and iron. Directly comparable arsenic results showed reductions of about 90-98%, with a representative value of approximately 95%. The results confirm that coordinated pretreatment, membrane treatment, controlled blending and continuous laboratory monitoring are essential for maintaining stable final-water quality under variable operating conditions.