This paper discusses the design of a 10 kV and 200 A hybrid dc circuit breaker suitable for the protection of the dc power systems in electric ships. The proposed hybrid dc circuit breaker employs a Thompson coil based ultrafast mechanical switch (MS) with the assistance of two additional solid-state power devices. A low-voltage (80 V) metal-oxide-semiconductor field-effect transistors (MOSFETs)-based commutating switch (CS) is series connected with the MS to realize the zero current turn-OFF of the MS. In this way, the arcing issue with the MS is avoided. A 15 kV SiC emitter turn-OFF thyristor-based main breaker (MB) is parallel connected with the MS and CS branch to interrupt the fault current. A stack of MOVs parallel with the MB are used to clamp the voltage across the hybrid dc circuit breaker during interruption. This paper focuses on the electronic parts of the hybrid dc circuit breaker, and a companion paper will elucidate the principle and operation of the fast acting MS and the overall operation of the hybrid dc circuit breaker. The selection and design of both the high-voltage and low-voltage electronic components in the hybrid dc circuit breaker are presented in this paper. The turn-OFF capability of the MB with and without snubber circuit is experimentally tested, validating its suitability for the hybrid dc circuit breaker application. The CSs' conduction performances are tested up to 200 A, and its current commutating during fault current interruption is also analyzed. Finally, the hybrid dc circuit breaker demonstrated a fast current interruption within 2 ms at 7 kV and 100 A.
13 October 2016 in IEEE Journal of Emerging and Selected Topics in Power Electronics
This paper presents the test results of an ultrafast (less than 2 ms) medium-voltage hybrid dc circuit breaker prototype that consists of three switching devices: a 15-kV silicon carbide (SiC) emitter turn-off thyristor as the main breaker (MB), a fast acting mechanical switch, and a commutating switch (CS) to quickly divert the primary current to the MB for arcless interruption. The hybrid dc circuit breaker prototype can interrupt a circuit in less than 2 ms in dc power systems up to 10 kV, such as in electric ships. The ultrafast operations and extremely low loss can effectively limit the fault current level and switching transients in all medium-voltage systems, and can provide intelligent and fast protection function for smart power distribution and critical loads in a modernized grid. The design considerations of the three switching devices of the hybrid dc circuit breaker are presented. This paper focuses on the ultrafast mechanical switch and the testing of the hybrid dc circuit breaker, while a companion paper addresses the high-voltage solid-state main switch and the low-voltage solid-state CS.
Analysis and experimental study of current commutation in an ultra-fast, current limiting, hybrid DC circuit breaker for medium voltage applications is reported in this paper. The hybrid DCCB consists a fast acting 15 kV mechanical switch, a low voltage commutating switch, a single 15 kV Silicon Carbide Emitter Turn Off Thyristor (ETO) device, and a stack of MOVs. The proof-of-concept prototype is able to conduct 45 A normal current and interrupt a maximum of more than 100 A fault current at medium voltage level in less than 4 milliseconds, which is one order of magnitude faster compared to conventional mechanical circuit breakers that typically take 40-100 ms. This paper has presented the operation principle of a hybrid DC circuit breaker and analyzed the current commutation process. Based on the analysis, guidelines are given in the paper to select and design the commutating switch.
17 August 2017 in IEEE Transactions on Industry Applications
An active damping method for Thomson coil actuated ultrafast mechanical switches is proposed, including its control. Ultrafast mechanical switches are crucial for both dc and ac circuit breakers that require fast-acting current-limiting capabilities. However, fast motion means high velocity at the end of travel resulting in over-travel, bounce, fatigue, and other undesirable effects. The active damping proposed in this paper not only avoids such issues but actually enables faster travel by removing limitations that would otherwise be necessary. This active damping mechanism is applicable in particular to medium- and high-voltage circuit breakers, but can be extended to actuators in general. A 15 kV/630 A/1 ms mechanical switch designed to enable the fast protection of medium voltage dc circuits is used as a testbed for the concept. The switch is based on the principle of repulsion forces (Thomson coil actuator). By energizing a second coil, higher opening speeds can be damped, resulting in limited over-travel range of the movable contact. The overall structure is simple and the size of the overall switch is minimized. To validate the concept and to study the timing control for best active damping performance, both finite element modeling and experimental studies have been carried out.
30 January 2020 in IEEE Transactions on Industry Applications
A novel design of the Z-source circuit breaker topology is presented to minimize on-state losses of the protection device. An ultrafast mechanical switch is proposed to commutate the fault current and improve the controllability of the circuit breaker. Replacing the power thyristor in the Z-source circuit breaker and integrating an advanced control scheme reduces energy losses with a low-resistance mechanical contactor. The proposed design facilitates bidirectional current flow, enhances control capability for distributed energy resources, and improves ride-through capabilities during load transients. Z-source circuit breakers utilize an impedance network to create a forced current zero crossing in the event of a fault, allowing the inline thyristor to isolate the fault from the source through reverse bias. However, full load current flows through the thyristor, resulting in high loss and heat generation. The concept is validated, and a proper control scheme is developed for this circuit breaker through an analytical estimation model of the system dynamics during a fault. Simulation and modeling are performed in power systems computer aided design (PSCAD) and piecewise linear electrical circuit simulation (PLECS). Finally, an experimental laboratory prototype is tested to validate the analytical and simulation models and certify the control logic.
A novel modification of the Z-source circuit breaker topology is presented for low voltage applications. An ultra-fast mechanical switch has been used in place of the solid-state switch (thyristor) in the Z-source circuit breaker to reduce the energy loss utilizing the very low resistance of mechanical contactors. The proposed modification also facilitates bi-directional current flow for distributed energy resource integration and improves ride through capabilities during downstream load transients. Existing Z-source circuit breaker designs utilize an impedance network to create a forced zero current crossing in the event of a fault in commutating thyristor to isolate the fault from source. However, all load current must flow through the thyristor during normal operation resulting in high loss due to on-state voltage drop of the solid-state switch. To validate the concept and develop proper control for this circuit breaker, both simulations and experimental studies have been carried out. The proposed breaker has been modelled in PSCAD for analysis. Additionally, an analytical estimation model of the system dynamics during fault has been developed to validate the simulations. A test circuit rated for 400 V and 20 A has been designed, constructed and tested.