As the U.S. electricity generation mix evolves and load growth accelerates, both energy storage and transmission become increasingly important sources of system flexibility and efficiency. However, their interaction is not well understood, especially for large, diverse regions. This study uses the Regional Energy Deployment System (ReEDS™) model to examine the joint planning of short-duration energy storage, long-duration energy storage, intrazonal transmission, and interzonal transmission in a modeled future U.S. electricity system. We apply cost multipliers to each storage and transmission type and evaluate 125 model cases across five scenarios representing different demand and technology futures. The results show storage and transmission are neither independent nor fully interchangeable. They interact through two channels: 1) direct but partial substitution between temporal and spatial flexibility and 2) indirect interaction through the generation portfolio they enable. When interzonal transmission becomes expensive, the system substitutes away from transmission expansion toward long-duration energy storage and, to a lesser extent, short-duration energy storage; when storage is more expensive, the system leans more on interzonal transmission. Lower short-duration energy storage cost shifts the system toward a more locally balanced resource mix with greater battery and solar deployment, whereas lower transmission cost favors greater interzonal transfer and resource sharing. Intrazonal transmission strongly shapes the generation mix: When local interconnection becomes more expensive, wind and solar deployment decline and the system rely more heavily on capacity that can be added or retained near existing grid infrastructure, especially natural gas combined-cycle plants, with some increases in nuclear and deferred coal retirements. Long-duration energy storage, represented by hydrogen storage, is deployed mainly when its cost becomes very low or when interzonal transfer is constrained, and it operates as a distinctly seasonal resource. Across all scenarios, the qualitative findings are robust, with stronger responses in higher-demand and more resource-intensive futures. These results suggest future U.S. grid planning should treat storage, intrazonal transmission, and interzonal transmission as linked flexibility resources rather than separate infrastructure categories.