Intermittent operation can improve the coefficient of performance (COP) of a ground source heat pump (GSHP) system. In this paper, an analytical solution to analyze the geo-temperature restoration performance under intermittent operation of borehole heat exchanger (BHE) fields is established. For this purpose, the moving finite line source model is combined with the g-function and the superposition principle. The model takes into account the heat transfer along the borehole, thermal interference between BHEs, and the influence of groundwater flow. The accuracy of the model is validated through comparison with an experiment carried out under intermittent operation. The model makes it possible to analyze the geo-temperature restoration performance and its influencing factors, such as BHE spacing, heat flow rate, operation mode, and groundwater flow. The main conclusions of this work are as follows. The heat transfer along the borehole should be considered when analyzing the geo-temperature restoration performance. When the BHE spacing increases, the soil temperature change decreases and the heat recovery improves. Therefore, adequate borehole separation distance is essential in the case of a multiple BHE system with unbalanced load. The presence of groundwater flow is associated with interference between the BHEs, which should not be ignored. In the case of long-term operation, the groundwater flow is beneficial to the geo-temperature recovery process, even for downstream BHEs. Finally, a greater groundwater flux leads to a better geo-temperature recovery.
15 May 2017 in Journal of Asian Architecture and Building Engineering
A reduced-scale (1:4) building corridor model was prepared to investigate the heat release rate (HRR) and smoke diffusion in a building corridor. Trays with heptane as fuel were used as fire sources. Three different sizes of trays were involved in this study to investigate the different HRRs. The results revealed that fire associated with larger trays exhibited a steeper power-law growth and decay. The temperature distributions in the corridor for the three cases showed similar tendencies. The temperature in the upper part of the corridor was relatively high, which decayed sharply along the corridor. However, the temperature in the lower part of the corridor was approximately the ambient temperature. Numerical simulation was also introduced to obtain more details regarding the temperature. The ceiling temperature was studied by using dimensionless parameters. The correlation between the ceiling temperature and the distance was fitted by using an exponential equation, and significant fitting results were obtained. Moreover, the vertical average temperatures in the corridor were also studied. The result indicated that greater HRRs led to higher vertical average temperatures with steeper growths and decreases.
In room–corridor building geometry, the corridor smoke temperature is of great importance to fire protection engineering as indoor fires occur. Theoretical analysis and a set of reduced-scale model experiments were performed, and a virtual fire model was proposed, to investigate the correlations between the maximum smoke temperature in corridors and the smoke temperature in rooms. The results show that the dimensionless virtual fire heat release rate (HRR) is characterized by quadratic-polynomial of the dimensionless smoke temperature in fire rooms. The dimensionless distance from a virtual fire source to the corridor ceiling varies linearly with the dimensionless smoke temperature in a room. Results of multiple regression indicate that, at the impingement area of virtual fire, the dimensionless maximum smoke temperature in corridors is only related to the dimensionless virtual fire HRR; in the non-impingement area of a virtual fire, the dimensionless maximum smoke temperature in corridors is a function of the dimensionless virtual fire HRR and dimensionless longitude distance. The viscosity and conduction exhibit an insignificant impact on the maximum temperature in the corridor. Through replacing the parameters of virtual fire with the dimensionless smoke temperature in fire rooms, the correlations between dimensionless maximum temperature in corridors and the dimensionless smoke temperature in fire rooms were proposed.
A reduced-scale compartment model was built to investigate the fire behavior in a confined compartment. Three different sizes of pool fire were involved in this study. And the fire behaviors in open space were also studied to compare with which in the confined compartment. The results shows the fire in confined space associated with larger pool exhibits a sharper growth and decrease in mass burning rate(MBR); meanwhile, a larger pool led to higher top MBR. When compare the fires in confined space with open space, the fires in open space got their top burning rate earlier, and they exhibited stronger and more frequent fluctuation. The influence brought by confined compartment on the fire was more pronounced in smaller pool fire. The processes of heat release rate (HRR) in confined compartment was also obtained.