The present study is devoted to the modeling, design, and experimental study of a heat pipe heat exchanger utilized as a recuperator in small air conditioning systems (airflow ≈ 300–500 m3/h), comprised of individually finned heat pipes. A thermal heat pipe heat exchanger model was developed, based on available correlations. Based on the previous experimental works of authors, refrigerant R404A was recognized as the best working fluid with a 20% heat pipe filling ratio. An engineering analysis of parametric calculations performed with the aid of the computational model concluded 20 rows of finned heat pipes in the staggered arrangement as a guarantee of stable heat exchanger effectiveness ≈ 60%. The optimization of the overall cost function by the “brute-force” method has backed up the choice of the best heat exchanger parameters. The 0.05 m traversal (finned pipes in contact with each other) and 0.062 m longitudinal distance were optimized to maximize effectiveness (up to 66%) and minimize pressure drop (less than 150 Pa). The designed heat exchanger was constructed and tested on the experimental rig. The experimental data yielded a good level of agreement with the model—relative difference within 10%.
Plate fin-tube heat exchangers are widely used in air conditioning and refrigeration systems and other industry fields. Various errors made in the manufacturing process can result in the formation of an air gap between the tube and fin. Several numerical simulations were carried out for a symmetric section of plate fin-tube heat exchanger to study the influence of air gap on heat transfer under periodic flow conditions. Different locations and sizes of an air gap spanning 1/2 circumference of the tube were considered for the range of airflow velocities. Velocity and temperature fields for cases with air gap were compared with ideal thermal contact cases. Blocking of heat flow by the gap leads to the reduction of heat transfer rate. Fin discontinuity in the front of the tube causes the smallest reduction of the heat transfer rate in comparison to the ideal tube-fin contact, especially for thin slits. The rear gap position is the worst in the smallest gap range. Therefore, reversing the flow direction can lead to up to a 15% heat transfer increase, if mainly the rear gaps are present. The introduction of a thin slit in the front of the tube leads to convective heat transfer enhancement, which should be further investigated.
The paper presents a numerical analysis of a tube-in-tube condenser of a small refrigeration system. One of the challenges in designing such units is to reduce their dimensions while maintaining the highest possible cooling capacity, so the research presented here focuses on the search for and impact of the appropriate flow conditions of these two fluids on condenser performance. The refrigerant is supercritical CO2, which is cooled by water. Thermal-flow simulations were performed for eight CO2 inlet velocities in the range of 1–8 m/s, and four cooling water velocities of 0.5–2 m/s. The main parameters of the exchanger operation were analyzed: heat transfer coefficient, Nusselt number, overall heat transfer coefficient, and friction factor, which were compared with selected correlations. The results showed that the condenser achieves the highest power for the highest water velocities (2 m/s) and CO2 (8 m/s), i.e., over 1000 W, which corresponds to a heat flux on the tube surface of approx. 2.6 × 105 W/m2 and a heat transfer coefficient of approx. 4700 W/m2K. One of the most important conclusions is the discovery of a significant effect of water velocity on heat transfer from the CO2 side—an increase in water velocity from 0.5 m/s to 2 m/s results in an increase in the heat transfer coefficient sCO2 by over 60%, with the same Re number. The implication of this study is to show the possibility of adjusting and selecting condenser parameters over a wide range of capacities, just by changing the fluid velocity.
21 August 2018 in Combustion Science and Technology
In the present work, we study numerically freely propagating flame in the stoichiometric propane–air mixture. The isothermal small tubes with one end fully open and the second one characterized by different degrees of opening are examined. The degree of opening of the tubes was equal to: 0% (completely closed), 25%, 50%, 75% and 100% (fully opened) of the tube cross-sectional area. Several mechanisms, such as thermal expansion of the burned gas which can leave the tube freely (fully opened left end of the tube), frictional forces and heat losses at the tube walls, movement of the unburned mixture generated by the propagating flame, occur simultaneously during flame propagation. Only the partial opening of the right end of the tube limits the flow of the unburned gas outside this end. This results in an additional pressure gradient and a rapid increase in velocity near the right end. The heat losses to walls cause that behind the flame pressure drops up to negative values. During propagation flames change their shapes and elongates. As a result of these mechanisms, we observe that flame speed change is almost linear for greater parts of tubes. This increase depends on the right end opening and tube diameter. Our examinations show that flame speed loses its linear relationship only for the bigger tube and right end opening in the range 75–100%. It suggests that heat losses to the wall restraint a sudden flame acceleration.
Different approaches to numerical simulation of vertical two phase closed thermosyphon are presented. Various Finite Volume Method models are cosidered – from simplified one phase to two phase with interface tracking/reconstruction algorithms. They are implemented using popular, commercial CFD code – ANSYS FLUENT. One phase simplified model considers only vapor flow without liquid phase (or with assumption of very thin liquid layer that can be ignored in problem formulation). Phase change processes are approximated by vapor mass sources (positive for evaporation, and negative for condensation). Magnitude of mass sources can be obtained by use of different source term correlations. Difference in two phase models lies in numerical method of solving Navier-Stokes equations – treating both phases as inter-penetrating (Eulerian-Eulerian) or distinct with sharp interface (VOF method). One phase simplified model is the most computationally inexpensive, but least physical and have to be supported by empirical correlations. Numerical problems are also present - e. g. with solving closed domain absolute pressure change caused by net mass source terms inequality (pressure change by increase of vapor mass inside thermosyphon). Two-phase methods are more physical, although expensive. VOF and Eulerian-Eulerian deal with two-phase flow, but rate of evaporation/condensation needs to be specified to match experimental data, most often by setting vaporization/condensation frequency coefficient (Lee model). Every model is analyzed and compared to others in terms of physical validity, implementation difficulties, solution time and convergence.
The article describes the numerical simulations of a heat exchanger section with a bundle of eight semicircular tube, either plain or connected with longitudinal wavy fins of four different lengths. The inlet velocity ranged from 0.433 to 4.33 m/s (Re=1,000-10,000), with study focused on pressure drop, total heat transfer rate and outlet temperature. The results indicate that fin elongation intensifies measured parameters. Com-pared to the plain tube configuration, wavy fins increased the heat transfer rate by 11%-108%, outlet temperature by 1%-5%, while the pressure drop by 11%-188%, depending on the fin length and inlet velocity. As a consequence, the JF-factor decreased by around 10%pt for every wavelength elongation in comparison to the plain semicircular tubes, with the highest value (80%) for case with the shortest fin. Although the investigated wavy fins provided by up to 21% higher heat transfer than straight‑fin semicircular tubes reported in the literature, they were accompanied by increased pressure losses, reaching up to 27%. The gathered results suggest further experimental investigation to confirm the effectiveness of wavy-finned semicircular tubes in the applications where the intensified heat transfer rate is required.