A transmission network’s main objective is to continuously supply electrical energy to consumers. This article presents an analysis of the use of multi-circuit, multi-voltage overhead lines as a compromise between ensuring the system’s safe operation by increasing the transmission network capacity and managing the constraints related to its expansion. The considerations presented in this work include the construction of such lines, their operation, and modeling aspects. As part of the study, the potential for improving the environmental conditions around the lines is discussed in terms of the necessary area for their construction and the peak electromagnetic field strength in their vicinity. We also present a mechanical analysis of stress and sag coordination in the individual circuits of these lines. Then, we detail the method for determining the electrical parameters of multi-voltage lines’ series impedances and capacitance. Specific attention is given to the possibility of zero-sequence voltage that occurs in the systems despite the symmetric supply and load of circuits—especially in the circuits with the lowest voltages—that result from the line’s geometric asymmetry. We evaluate the impact of the line’s geometric asymmetry on the power system’s correct operation by determining the asymmetry factors. Finally, the accuracy of using a simplified symmetric model for lines with various geometric asymmetries is analyzed by studying the error of the short-circuit currents.
Wydawnictwo SIGMA-NOT wydaje czasopisma fachowe informuj?ce swoich czytelnik?w o najnowszych osi?gni?ciach naukowych i nowoczesnych rozwi?zaniach technicznych w Polsce i na ?wiecie, popularyzuje problemy techniczne oraz poszerza wiedz? i kultur? techniczn?.
Multi-circuit, multi-voltage overhead lines (MMOLs) are becoming a favorable solution in the perspective of ensuring the efficient transmission of electrical energy and limitations relating to the expansion of the transmission network. The main part of this manuscript contains a method that minimizes the effects of risks on the operation of the power system due to asymmetrical MMOLs, with particular emphasis on the circuit with the lowest-rated voltage. The selected set of criteria includes elements such as the determination of the neutral point displacement voltage in the network with the lowest-rated voltage (zero voltage, U0), selected voltage quality factors, and short-circuit analyses to examine the impact of differences between the use of accurate and simplified mathematical models on the calculation of short-circuit currents. Methods to minimize the effects of MMOL geometric asymmetry have been proposed using simple technical steps, such as selecting the appropriate pole silhouette (indication of the methodology for identifying such supporting structures), changing the way of supplying individual circuits, or using partial transposition in the circuit with the lowest-rated voltage. The proposed methods are verified by analyzing a case study of the development of the transmission network in Poland.
The core objective of transmission tariffs is the recovery of costs related to the transport of electricity. A usual component of a tariff is a fixed charge that covers the costs of the network infrastructure. As many customers use the power grid, the rate of this charge should reflect, as closely as possible, the actual costs of supplying energy to the individual consumers. These costs result from which network elements have been used in delivering the electricity, and to what extent these elements have been used. Therefore, the fixed transmission rates should depend on the degree of network utilization. This article investigates definitions of the degree of network utilization based on the active power flow. To calculate the degree of network utilization, the flow of electricity on a branch must be decomposed into the streams flowing to individual customers. For this decomposition, two methods are examined: a power flow tracing method, based on the proportional sharing principle, and an incremental power flow method, based on the superposition principle. The analyzed methodology is applied to a small test system for conceptual discussions, as well as to the transmission network of the Polish power system, as an example of practical application. The results of this study were then compared with the commonly used “postage stamp” method. Finally, several practical aspects related to the potential implementation of the presented methodology are discussed.
W artykule omówiono i porównano wybrane cechy wysokonapięciowych układów przesyłowych, tj. klasycznych linii WN i NN, napowietrznych linii wielonapięciowych, linii HVDC oraz hybrydowych. Problem przesyłu dużych mocy na znaczne odległości występuje w wielu krajach Europy i świata, głównie ze względu na pojawiające się duże koncentracje mocy wytwórczych m.in. w morskich farmach wiatrowych. Problemy te znajdują również odzwierciedlenie w przedstawionym do opiniowania planie rozwoju sieci przesyłowej w Polsce na lata 2023-2032, który zakłada m.in. budowę lądowego połączenia HVDC z północy na południe KSE.
The paper discusses aspects related to modeling the capacitances of multi-circuit multi-voltage overhead power lines (HV, EHV). The problem of neutral point displacement under the influence of the capacitive asymmetry of such lines was considered. The results of analyses were presented for selected real multi-circuit multi-voltage overhead line constructions with varying degree of geometrical asymmetry.