Supraharmonic propagation depends on the impedance of both the grid and the devices connected to it. Few attempts to quantify the impact of the customer’s load variability have been done. The interest of grid operators is in counteracting the supraharmonic propagation upstream to maintain power quality. Quantifying the impact of impedance on supraharmonic propagation gives information to strategically counteract this propagation to the grid. This article presents a method for analysis of supraharmonic propagation that uses a stochastic approach to describe the impact of low-voltage (LV) loads. Scenarios of a strong and a weak grid are presented to study the impact of reinforcement grid measures.
27 May 2020 in IEEE Open Journal of Industry Applications
This paper addresses the accelerated aging of medium-voltage (MV) cable terminations with resistive stress-grading due to supraharmonics. The paper introduces a simple and quick way to relate the risk of cable termination failure to the characteristics of supraharmonic distortion in the system. The motivation is to give practical recommendations and guidelines to evaluate the risk of failure of cable terminations under the presence of supraharmonics in MV networks. The underlying model relates the heating in the cable termination linearly with the frequency of the voltage applied and proportionally with the square of the magnitude of the voltage. The indicator can be used to decide whether given levels and frequencies of supraharmonics in the MV network represent a risk to cable terminations. The parameters of the cable termination design are not needed for that decision. However, the decision criterion is based on one sample data (Eagle Pass) and more field information is crucial to improve the approach.
Power converters with high switching frequency used to integrate renewable power sources to medium and low voltage networks are sources of emission in the supraharmonic range (2 to 150 kHz). When such converters are connected to a medium voltage (MV) network these supraharmonics propagate through the MV network and can impact network and customer equipment over a wide range. This paper evaluates an existing Swedish MV electrical network and studies the pattern of supraharmonic resonance and the propagation of supraharmonics. The MV network consists of eight feeders including a small wind farm. Simulations reveal that, the bigger the MV network, the more resonant frequencies, but also the lower the amplitude of the resonance peaks in the driving point impedance. It was also identified that for short feeders as length increases, the magnitude of the transfer impedance at supraharmonic frequency decreases. For further increment in feeder length, the magnitude increases or becomes almost constant. For very long feeders, the transfer impedance further starts decreasing. The eight feeders in the network under study are similar but show completely different impedance versus frequency characteristics. Measurements at the MV side of the wind farm show time varying emissions in the supraharmonic range during low power production. The impact of these emissions coupled with system resonance is examined.
28 September 2020 in IEEE Open Journal of Industry Applications
Due to the increase in electronic loads such as LED lamps, power supply units for computing loads, voltage frequency drives in industries; high-frequency distortion is introduced into the power system. These high-frequency components appear due to the switching components of different power electronic converters present in the mentioned loads. The switching frequency components are most often in the range of 2 kHz to 150 kHz referred to as supraharmonics. The paper aims to show, with simulations and measurements, how supraharmonics sum in neutral and to quantify the neutral supraharmonic current as a ratio of single-phase current. This paper defines characteristics of supraharmonic emission that influence their summation in the neutral conductor through studies of devices connected in a balanced three-phase four-wire system. The paper further defines the relation of the supraharmonics emission with the number of devices connected at each phase. A mathematical model to predict the supraharmonics in a neutral conductor based on single-phase current and the number of devices is further proposed.
30 June 2020 in Renewable Energy and Power Quality Journal
This paper shows a study of the variations of the supraharmonic distortion emitted by an LED lamp during and after its thermal stabilization. The study is aimed to contribute to map the uncertainties existing when quantifying supraharmonics. Measurements of the current drawn by five lamps of the same type and manufacturer are performed. Then, analysis in the frequency domain is performed and the Total Supraharmonic Current (TSHC) index is used to quantify the supraharmonic emission of the lamps. The TSHC is calculated over bands of different widths, whose outcomes are then compared to decide which bandwidth results in a less time-varying-TSHC index. It is demonstrated that the supraharmonic distortion emitted by the lamp under study experiences both an increase in magnitude and a shift in frequency during the thermal stabilization of the lamp. It is also shown how the frequency grouping impacts the quantification. It is concluded that the best choice of a grouping bandwidth is one wide enough so that it includes the whole emission band of interest. This result is a step forward to set up references for the analysis and quantification of broadband supraharmonic emission.