When a grid-connected inverter is connected to a weak grid, the system may be instable. An active damper can be connected to the point of common coupling (PCC), which simulates a virtual resistor to damp the resonance and thus stabilize the system. In this paper, an adaptive tuning method of the virtual resistor is proposed, which can automatically regulate the virtual resistor to the critical value to stabilize the system, and thus reduce the power loss. Furthermore, the active damper is designed not to respond to the dominant low-frequency harmonic components in the PCC voltage introduced by the grid background harmonics, so that its power loss can be further reduced. In order to make the active damper more accurately simulate the virtual resistor in a wide frequency range, a harmonic-current-reference compensation method is proposed. The prototypes of a 6-kW grid-connected inverter and a 1-kVA active damper are built and tested to verify the effectiveness of the proposed control scheme of the active damper.
6 March 2017 in IEEE Transactions on Power Electronics
The injected grid current of the voltage-controlled grid-connected inverter has serious distortion due to the low frequency harmonic components in the output voltage, which is resulted by the dead time of the drive signals of the power switches, and the distortion cannot be eliminated even when an output voltage closed loop is incorporated. This paper introduces a virtual series impedance to increase the output impedance of the grid-connected inverter only at the dominated lower harmonic frequencies; thus, the injected grid current quality can be improved and the dynamic performance of the grid-connected inverter is not deteriorated. Experimental results from a 6-kW single-phase grid-connected inverter confirm the effectiveness of the proposed method.
5 March 2018 in IEEE Transactions on Power Electronics
The three-phase four-wire inverter with split dc-link capacitors can supply unbalanced loads. For the purpose of reducing the filter inductors, a neutral inductor could be introduced into the neutral line. This paper analyzes the operation principle of three-phase four-wire inverter with split dc-link capacitors when a neutral inductor is introduced. It is illustrated that the neutral inductor can reduce the zero-sequence switching harmonics in the voltages between the phase-leg midpoints and the output neutral point, thus the filter inductors can be reduced. The optimized design of the neutral inductor and filter inductors is proposed with the considerations of the inductor current ripple, the ability of supplying unbalanced loads and the total energy stored in the inductors. The equivalent circuits of the three-phase four-wire inverter with split dc-link capacitors and neutral inductor is derived in the α–β–0 frame, and the zero-axis voltage regulator is modified to suppress the third-order harmonic in the zero-sequence current caused by the dead time of the drive signals for the power switches. Finally, the experimental results from a 9-kVA prototype are provided to prove the effectiveness of the proposed optimized design of the neutral inductor and filter inductors and the control strategy of the inverter.