This paper widens the application of a testing protocol for overhead line insulators introduced by TERNA. Testing results relevant to three groups of Room Temperature Vulcanized pre-coated cap-and-pin insulators removed from High Voltage Alternate Current and Extra-High Voltage Alternate Current Italian lines after different years of service are reported and statistically processed; the third group is treated here for the first time and new results for the other two groups are included. Among the various tests prescribed in the protocol, focus is on the Quick Flashover test, with the aim to examine and compare the flashover voltages of all three groups as a function of service time. The dependence of flashover voltage on electric field is also analyzed and a model correlating flashover voltage with field and time is proposed for the first time. It is confirmed that the flashover voltages provided by the Quick Flashover test can be considered as a diagnostic property of Room Temperature Vulcanized insulators, as they drop with the ageing time and the electric field.
The reliability of the national power grid is a key issue in modern society. Atmospheric aerosols are the main cause of the reduction in the performance of insulators and the increase in the possibility of flashovers, resulting in power line failures. Under high ambient humidity, the water-soluble compounds of atmospheric aerosols collected on the insulators’ surface can dissociate in ions and form a conductive layer, which may lead to flashover events. With a view to investigating the processes that drive these phenomena, the chemical composition of aerosol deposits on insulators in Italy was determined by ion chromatography analysis and thermos-optical and X-ray techniques. In addition, a synthetic aerosol with the same analyzed chemical composition was generated in a laboratory and deposited on PTFE filters and glass specimens allowing us to determine the deliquescence and crystallization relative humidity and the conductive effect in an aerosol exposure chamber. The results evidenced the presence of a hazardous inorganic ion layer, which generates a sharp phase transition of the aerosol deposit as a function of the ambient relative humidity; this layer poses a dangerous threat to the reliability of the power grid, increasing the probability of flashover events where the conductive layer facilitates the flow of electrical current across the insulator surface, potentially causing power outages or damage to the power lines.