One of the main cause of damages for wind turbine power plants is certainly constituted by lightning. Direct and indirect events can indeed produce damages and malfunctions of electrical and mechanical components. Concerning mechanical components, blades and bearings are the most involved parts. In particular, lightning-damages produced at bearings positioned at the mechanical interface between rotating parts of the wind turbine, can result in high costs, considering the difficulties involved in the replacement of such components. The paper presents a numerical and an analytical model of wind turbine main shaft bearings aimed at calculate their electrical impedance along with their experimental validation. These models provide useful criteria for the design of wind turbines lightning protection systems (LPS). In this respect, the paper presents also the development of a specific LPS for the protection of wind turbine bearings and the relevant effectiveness analysis obtained by means of experimental tests.

1 March 2023 in IEEE Transactions on Electromagnetic Compatibility
Verified
Journal Article
Open access
GLGianfranco Di Lorenzo
Gianfranco Di Lorenzo
ESErika Stracqualursi
Erika Stracqualursi
Massimo MarzinottoMassimo Marzinotto
Massimo Marzinotto
JFJose Brandao Faria
Jose Brandao Faria
Rodolfo ARANEORodolfo ARANEO
Rodolfo ARANEO
The computation of sea/seabed-return distributed parameters of subsea cables is a relevant topic due to the growing importance of submarine connections. This article presents for the first time new formulas for the computation of self and mutual ground impedances and admittances for submarine cables buried in the seabed. The original theory developed by Sunde is applied to a three-media model with air, sea, and seabed. Referring to the practical installation practice of the Italian transmission system operator Terna S.p.A., we compare the prediction of the available models and assess the effect of the different approximations on the computation of the per unit length ground parameters. Finally, we define the limits of applicability of the available models that differ in accuracy and complexity.

4 December 2009 in Electric Power Systems Research
Verified
Journal Article
Closed access
Massimo MarzinottoMassimo Marzinotto
Massimo Marzinotto
CPCarlo Mazzetti di Pietralata
Carlo Mazzetti di Pietralata

1 July 2007
Verified
Conference Paper
Closed access
AKA. Kern
A. Kern
GDG. Dikta
G. Dikta
ZFZ. Flisowski
Z. Flisowski
Massimo MarzinottoMassimo Marzinotto
Massimo Marzinotto
CPCarlo Mazzetti di Pietralata
Carlo Mazzetti di Pietralata
In the present paper data collected from the field related to the damage statistics of electrical and electronic systems due to lightning overvoltages are reported. These damages were registered by German insurance companies in 2005 and 2006 in different structures and installations. With the use of stochastical methods it is possible to reassess the collected data and to define cases, which are with high probability caused by lightning overvoltages. The results of the stochastic model are compared with the probability of damage distributions obtained by using the analytical method, which is the basis for the IEC Standard rules.

1 July 2007
Verified
Conference Paper
Closed access
Massimo MarzinottoMassimo Marzinotto
Massimo Marzinotto
The knowledge of the statistical distribution of the overvoltages stressing the insulation of a cable line is fundamental for the insulation coordination. The estimation of such distributions requires the utilization of complex numerical programs. In this paper a simplified method which takes into account a typical configuration in a power system "overhead line - cable line - transformer" is introduced. The results, although in a general form, highlight that the knowledge of an overvoltage reduction factor, estimated once for all for different cables and power system configurations, can be used to evaluate in an easy way the distribution of the overvoltages stressing the insulation of a cable line starting from the statistical distribution of the overvoltages impinging the cable line.

28 June 2024 in Energies
Verified
Journal Article
Open access
PDF file
Bassel DibanBassel Diban
Bassel Diban
Giovanni MazzantiGiovanni Mazzanti
Giovanni Mazzanti
Massimo MarzinottoMassimo Marzinotto
Massimo Marzinotto
ABAntonio Battaglia
Antonio Battaglia
This paper aims at estimating the life of extruded HVDC cable insulation subjected to fast and slow voltage polarity reversals (VPRs). An ad hoc MATLAB code is used for the transient electric field simulation in the cable insulation thickness by solving numerically Gauss, ohm, and current continuity equations beside a macroscopic conductivity equation. A transient temperature is also considered during slow VPR transients. The results show a significant localized reduction in the life of the inner insulation, making the life distribution non-monotonous inside the insulation thickness. The results show that fast VPRs are the most stressing transients in this study. The longer the duration of the zero-voltage period in slow VPR, the less stressed the insulation, hence, the longer the local life in the inner insulation of the cable. The latter is justified by the charge relaxation during slow VPRs.