The condition of each cup-and-pin insulator that forms a string must be considered in order to obtain effective guidance for contamination flashover mitigation. This paper describes an approach to assess the string condition based on the ultraviolet (UV) emitted by each cup-and-pin insulator during partial discharge condition. The UV patterns on the string were observed visually in the laboratory test. The criteria of string condition level was built based on the patterns and applied to the strings installed in the field. The index value expressing the string condition level in the field (level status) was then compared with the UV quantitative parameter extracted from the UV video. At the final stage, a logarithmic regression classification model was built based on these two values. The laboratory test results showed that there were three levels of string condition, namely level one (safest), level two, and level three (most dangerous). Most strings in the field had category level two, while most strings with level three were of the suspension type. The UV emission area parameters expressed in pixels and percentages were able to represent the sporadic nature of the discharge phenomenon. The proposed approach provided a predictive model with a mean absolute error of 0.182.
Contaminants in transformer oil insulation can float when meeting several conditions. Then, the presence of floating contaminants affects the electrical characteristics of oil insulation. Therefore, the pre-breakdown (corona) and breakdown characteristics due to metallic floating particles in transformer oil insulation would be investigated. This test used DC high voltage stress. A 56 Ω resistor was connected to the oscilloscope to detect the corona currents. The camera was used to capture the images of corona light emission. In addition, the electric field between the electrode and particles was simulated. The variables were the particle size, including its shape, and the distance between the particles and the grounded electrode. The experimental results show that the average value of corona inception and breakdown was inversely proportional to the size of floating particles. The peak value of corona current was directly proportional to the particle size. The lowest breakdown voltage was found when the particle was close to the electrode, but they were not in contact.