The number of elderly living in small-scale senior citizen welfare institutions in Taiwan has been increasing. Hence, enhancing the quality of care and safety of the residents in these institutions is a pressing issue. Our research team visited and reviewed data on 53 small-scale institutions in Tainan based on in-depth fire protection defense strategies and proposed a three-layer protection mechanism. The results showed that: (1) half (50%) of these institutions only meet the old anti-seismic system; (2) 26 (49%) institutions have multi-story buildings, thus, more staff needs to be arranged for night shifts to enable emergency responses on each floor; (3) all institutions have fire detectors; (4) 84% of the elderly living in these institutions are mobility-impaired and need to rely on the assistance of staff for evacuation; (5) most institutions (91%) employ foreign female caregivers which mostly work on night shifts; thus, routine training of emergency response should also consider the abilities of the foreign caregivers; (6) 35 (66%) institutions arrange only 50% of the day-shift manpower for the night shift; (7) 37 (70%) institutions should evaluate whether the function of their fire detectors is affected by fan air; and (8) 11 (21%) institutions use inflammable materials for furnishings to create a “cozy” atmosphere. This study also suggests that preventing smoke from spreading from a room that is on fire to other areas is an important evaluation item. Hopefully, these findings can serve as a reference for countries that are facing an increasingly aging population.
Providing high-quality care services and fire safety for long-term care institutions is an important issue in Taiwan, which became an aging society in 2018. The fire incidents in Taiwan over the years show that nighttime fires in care institutions often cause serious casualties. It is necessary not only to understand the causes of serious nighttime fire incidents that have occurred but also to draw lessons from the fires that have been put out without causing injuries. In this study, the top two serious nighttime fire accidents in long-term care institutions in the past two decades in Taiwan were analyzed based on the publicly official and academic literature utilizing fire protection defense-in-depth strategies. For comparison, two other nighttime fire cases with similar scenarios but no casualties were also analyzed in depth about the cause of no casualties. The buildings of the four nighttime fires were equipped with fire protection equipment in their public areas. The theoretical basis of the research is the fire protection defense-in-depth strategy. In both categories of severe casualties and no severe casualties, one was caused by arson and the other one by an electrical fire, with the ignition point of a fire in the storeroom and the other in the ward. However, the end results were quite different. The analyzed results showed that the severe fires lasted for about an hour, while the fires without casualties were put out within 15 min. A well-constructed second layer of defense measures could effectively contain a fire, and an effective third layer of measures could avoid casualties. The death rate of personnel can be reduced from a dozen to zero, and the burning time is also greatly reduced. The results could be used as a reference for emergency measures in long-term care institutions.
7 December 2020 in International Journal of Ventilation
In some countries, test standards have been adopted which measure the effectiveness of smoke exhaust systems in clearing out heat and smoke produced separately. However, because these standards provide no quantitative provisions for dealing with the amount of visual smoke, there is an unclear correlation between the amount of smoke generated and the fire load. This paper applied the homogeneity concept of using a smoke collection box to examine the smoke generation rate of a smoke generator using CO2 as the driving gas. To avoid using the previous visual method of judging the rates, this research used measurement equipment to conduct a scientific analysis. Thus, the results were more objective. The equipment used included a Closed-Circuit Television (CCTV) Camera, a thermocouple, a traditional P-type smoke detector, a digital R-type smoke detector, and light attenuation measurement equipment. Under release pressures of 40, 60 and 80 psi, a 15% smoke density required smoke generation at 6.50, 8.42 and 10.46 m3/s, respectively. Achieving a homogeneous distribution of smoke within the space was accomplished. The data obtained in the test could be used not only to judge the efficiency of a smoke exhaust system but also provide adjustment information for a smoke exhaust system.
Elderly welfare institutions in Taiwan have experienced multiple severe fire incidents, with smoke inhalation accounting for the majority of fatalities. Hot smoke can rapidly propagate through interconnected ceiling spaces, complicating evacuation for residents with limited mobility who depend heavily on caregiving staff and external responders. Field inspections conducted in this study indicate that 82% of residents require assisted evacuation, underscoring the critical role of early detection, staff-mediated response, and effective smoke control. Drawing on disaster management theory, this study examines key determinants of fire safety performance in elderly welfare institutions, where caregiving staff are primarily trained in medical care rather than fire safety. A total of 64 licensed institutions in Tainan City were investigated through on-site inspections, structured checklist-based surveys, and statistical analyses of fire protection systems. In addition, a comparative review of building and fire safety regulations in Taiwan, the United States, Japan, and China was conducted to contextualize the findings. Using the defense-in-depth framework, this study proposes a three-layer fire safety strategy comprising (1) prevention of fire occurrence, (2) rapid fire detection and early suppression, and (3) containment of fire and smoke spread. From a sustainability perspective, this study conceptualizes fire safety in elderly welfare institutions as a problem of risk governance, illustrating how defense-in-depth can be operationalized as a governance-oriented framework for managing fire and smoke risks, safeguarding vulnerable older adults, and sustaining the resilience and continuity of long-term care systems in an aging society.
Air curtain systems have been proposed as a supplementary smoke control strategy for vehicle tunnels, particularly where structural constraints limit the installation or upgrading of conventional ventilation systems. However, most previous studies rely on numerical simulations or fixed experimental facilities, while flexible experimental platforms and the influence of vehicle obstruction on smoke behavior remain less explored. This study experimentally investigates the smoke confinement performance of an air curtain using a 1:18 modular detachable scaled vehicle tunnel model. The modular configuration enables flexible assembly and adjustment of the experimental setup for different test conditions. A series of laboratory experiments was conducted using a liquefied petroleum gas (LPG) burner to simulate a vehicle fire. Temperature measurements and smoke visualization were performed under different air curtain jet velocities and vehicle obstruction conditions to analyze the interaction between the air curtain jet and buoyancy-driven smoke flow. The results show that the air curtain significantly restricts the upstream propagation of hot smoke and modifies the thermal field inside the tunnel. When the jet velocity reached approximately 5 m/s, the temperature in the protected region decreased by about 25–35% compared with the case without an air curtain. In addition, the presence of vehicle models altered the airflow structure and increased heat accumulation in the middle region of the tunnel cross-section. These results demonstrate that the proposed modular tunnel model provides a reliable experimental platform for tunnel fire research and highlights the importance of considering vehicle obstruction effects in tunnel smoke control studies.