To reveal the influence of urban high-voltage cable tunnel networked structure on the fire spread characteristics, and to provide a basis for the fire prevention and control and structural design of cable tunnels. In this paper, a full-scale field test was carried out in an urban underground cable tunnel, and a smoke spread model was constructed by using numerical simulation of fire dynamics with different structural characteristics of the tunnel coupled with the ventilation system. The fire dynamics numerical simulation is used to construct a smoke spread model coupling different tunnel structural characteristics and ventilation system. This study numerically analyzes smoke dynamics in urban cable tunnel node fires, examining the effects of tunnel structure, cable layout, ventilation, and fire source location on temperature, CO distribution, and smoke exhaust efficiency. Results show that T-shaped nodes trap heat and increase CO concentration by 14% in the fifth layer, while Cross-shaped nodes promote diffusion, lowering ceiling temperatures by 5% but reducing exhaust efficiency. Horizontal cable layouts enhance oxygen permeability by 32%, raising fire temperatures to 820°C, whereas stacked layouts increase fourth-layer CO by 58%. A 1.2 m/s lateral wind intensifies combustion, unexpectedly raising ceiling temperatures. Mechanical exhaust strategies show that low thresholds cause instability, while high thresholds expand smoke spread risks. Fire-source location affects CO behavior, with turbulence at nodes enhancing stability. This study proposes flow-guiding optimization and real-time control strategies, offering theoretical support for tunnel fire protection. Future research should integrate experiments for refining critical parameters.
Transformer jet fire is one of the most serious types of substation fire accidents, which often causes heavy casualties and property losses and even causes other secondary disasters, further expanding the impact of thermal disasters. Compared with the jet fire formed by the leakage of gaseous combustibles during production, transportation, and storage, the research on the combustion behavior of transformer jet fire under multiple factors, such as flame shape and flame height, is relatively scarce. This study used the research method of combining experimental research with theoretical analysis. Flame shape and flame height of transformer jet fire under different vessel diameters (5, 8, and 10 cm), opening diameters (5, 10, and 15 mm), and filling rate (60, 80, and 100%) were measured and analyzed. The results show that jet momentum and flame buoyancy are the main reasons for the change in flame shape characteristics. The transformer jet fire development process can be divided into three typical stages of full development, stable jet, decay, and extinguish. The flame height increases with the increase of the opening diameter and container diameter, and increases first and then decreases with the increase of filling rate. The functional relationship between the flame height and the 0.2 power of the characteristic Froude number is established. The research results provide reliable theoretical guidance and data support for transformer fire prevention and control.
The underground power houses of pumped-storage power stations (PSPSs) are highly complex, with interconnected and multidimensional structures, including various tunnels, such as the main and auxiliary power houses (MAPH), main transformer tunnel (MTT), tailrace gate tunnel (TGT), access tunnels (ATs), cable tunnels (CTs) etc. During intensive civil construction and electromechanical installation, fire risk becomes particularly prominent. Current research mainly examines fire incidents within individual tunnels, lacking comprehensive analyses of smoke spread across the entire cavern network. Therefore, in this study, a numerical model of a cavern complex in a PSPS was established to analyze smoke behavior and temperature distribution under various fire scenarios. The results indicated that when a fire occurred in the MAPH, the fire risk was relatively higher compared to fires in other places. Using the example of smoke spread from the MAPH to the MTT, the smoke spread process through key connecting caverns was analyzed. Initially, the temperature and velocity were stable, and the CTs and traffic cable tunnel in the auxiliary powerhouse (TCTAP) were the main smoke paths. After 7 min, the heat release rate (HRR) became stable, and CTs and ATs became the main paths for smoke spread, which could provide a reference for improving fire design in underground cavern systems.
Jet fire is a kind of instability behavior in the combustion process of a transformer. Once the jet fire occurs, the typical characteristic parameters of the fire change nonlinearly, which brings uncertainty and danger to the emergency response. The current research mostly focuses on the combustion instability mechanism of oil-filled equipment under the action of an external heat source and pays little attention to the mechanism and critical criterion of jet fire formed by transformer leakage combustion instability. The leakage combustion of the transformer leads to the dynamic change of thermodynamic state parameters of the medium, and the mechanism of overpressure induced by the phase transition from metastable to unsteady state is not revealed. It is of great significance to study the formation mechanism and critical criterion of transformer jet fire for explaining the dynamic competition behavior between the internal gas production rate and discharge rate during transformer combustion. In this study, the heat loss experiments of transformer oil under different heating rates were carried out, the boiling range of transformer oil was obtained to be 102-300 °C, and the average activation energy was 65.41 kJ/mol. Experiments on the formation mechanism of transformer jet fire under different fire power were carried out, the phase characteristics of the jet release of transformer oil were elucidated, and it was clarified that overpressure was the driving force for the occurrence of the fire. It was found that the key criteria for the formation of a jet fire are a transformer oil temperature of 300 °C and a pressure rise rate of 0.001 kPa/s. The results of this study will help firefighters and rescuers to formulate a more scientific, rational, and safer fire-fighting strategy.
Full-scale fire tests were conducted in a 331 m long urban underground cable tunnel to investigate how fire source area, cable layer number, and spatial arrangement jointly affect combustion, temperature evolution, and smoke toxicity. Eleven Case were designed by varying fuel tray area and volume, cable layers (0–5), and multilayer versus dense single-layer layouts. Enlarging the fire source significantly increased the mass loss rate and total fuel consumption, indicating stronger combustion. More cable layers raised ceiling peak temperature and prolonged high-temperature duration due to enhanced heat feedback. Stratified multilayer cables produced a stable high-temperature ceiling zone, whereas dense single-layer cables caused rapid heating but lower peaks and faster cooling because of local oxygen depletion. Higher cable load and denser layouts markedly reduced visibility and increased CO concentration and persistence. These findings deepen the understanding of fire behavior in urban underground cable tunnels and provide a scientific basis for optimizing safety design and emergency response strategies.