A dynamic rotor interturn short circuit fault may occur during synchronous generator operation. However, there is no method to analyze the generator’s characteristics under the dynamic rotor interturn short circuit fault and identify the fault. In order to solve this problem, a new dynamic rotor interturn short circuit fault analysis model is creatively proposed through mathematical derivation. Firstly, the rotor vibration characteristics and the mechanical response under magnetic pull excitation are theoretically analyzed. In addition, a finite element modeling method for the dynamic rotor interturn short circuit fault is proposed, and an experimental device is designed. The model of a synchronous generator under the dynamic rotor interturn short circuit fault is established to obtain the rotor’s unbalanced magnetic pulls and mechanical responses by finite element calculation. Finally, the rotor vibrations are tested on a CS-5 prototype generator. The validity of the model is verified by finite element calculation and an experiment. This paper provides theoretical support for the diagnosis of a synchronous generator’s dynamic rotor interturn short circuit fault.
This paper studies the electromechanical characteristics of synchronous generators under dynamic stator interturn short circuit (DSISC). First, the air gap magnetic flux density (MFD) of the generator under normal and DSISC fault was obtained. Then, the expression for the phase current and the electromagnetic torque (EMT) were obtained. After this, the phase current and EMT were analyzed by finite element analysis (FEA). Finally, the measured electromechanical characteristics of the CS-5 generator under different conditions were analyzed in accordance with theory and simulation. It was shown that with the occurrence, and deterioration, of DSISC, the amplitude of the first harmonic, third harmonic and fifth harmonic of the phase current became more affected by the pulse. Meanwhile, the even-numbered harmonics components of EMT increased.
This paper analyzes the electromagnetic torque (EMT) fluctuation characteristics in synchronous generators under rotor interturn short-circuit (DRISC) fault. The novelty of this paper is that the DRISC fault is proposed based on the intermittent interturn short circuit existing in the actual operation and compared with the static rotor interturn short-circuit (SRISC) fault. In the work, by studying the influence of DRISC with different positions and different short-circuit degrees, the fluctuation characteristic of the EMT is analyzed and verified. The results show that when the DRISC5% fails, the location is in slot 3, the amplitude of first harmonic decreases by 7.2%, second harmonic amplitude increases by 33.4%, third harmonic decreases by 4.3%, and fourth harmonic increases by 26.8%. As the degree increased and positioned away from the large tooth of the DRISC, the overall EMT amplitude and reverse pulse increased, first and third harmonics decreased, and second and fourth harmonics increased.