The smart electricity meter (SEM) is an important part of smart power grid, and the accuracy of SEMs is the basis for power grid operation control and trade settlement between power supply and electricity consumption, but the evolution behaviors of metering error of SEMs under field operation conditions have not yet been identified. The SEMs were installed and operated on site, metering error data were collected under various temperature and current conditions. The influences of current, power coefficient, and temperature on metering error and consistency were analyzed separately with the help of quadratic polynomials, and then an integrated model elaborating the joint effects of multi-stress was developed based on a binary quadratic polynomial. We find that a lower temperature and a larger current result in a higher metering error of SEMs; however, the effects of current on metering error are determined by power coefficients. The results have reference value for remote metrological verification, error monitoring, and the optimization of the operation and maintenance scheme of SEMs.
It is helpful to have a replacement strategy by predicting the number of failures of in-service electricity meters. This paper presents a failure number prediction method for smart electricity meters based on on-site fault data. The prediction model was constructed by combining Weibull distribution with odds ratios, then the distribution parameters, failure prediction number, and confidence intervals of prediction number were calculated. A strategy of meter replacement and reserve were developed according to the prediction results. To avoid the uncertainty of prediction results due to the small amount of field data information, a Bayesian failure number prediction method was developed. The research results have value for making operation plans and reserve strategies for electricity meters.