Frequency estimation is vital for monitoring, control, and protection of power systems. Multiple signal classification (MUSIC) method has been used for frequency estimation in communication systems. This method requires wide range of frequency scanning and heavy computations, which is inappropriate for power system applications. This paper proposes an adaptive accelerated MUSIC algorithm for frequency estimation in power systems. The algorithm accelerates the frequency scanning and adapts itself to transient conditions of power systems, to keep the accuracy of the frequency estimation with minimum computations. Experimental signals besides several static and dynamic test signals are used to evaluate and compare the performance of the proposed algorithm with recent methods. These comparisons show that the proposed algorithm provides faster convergence speed, lower computation burden, and more robustness to noise and grid disturbances. These significant advantages make the proposed algorithm appropriate for power system protection and control applications.
14 May 2019 in IEEE Transactions on Signal Processing
In this paper, we address the problem of recovering point sources from two-dimensional low-pass measurements, which is known as the super-resolution problem. This is the fundamental concern of many applications such as electronic imaging, optics, microscopy, and line spectral estimations. We assume that the point sources are located in the square [0,1] 2 with unknown locations and complex amplitudes. The only available information is low-pass Fourier measurements band limited to the integer square [-f c , f c ] 2 . The sources are estimated by minimizing the total variation norm, which leads to a convex optimization problem. We observe in numerical results that if the sources are closer than 1.4/f c , they might not be recovered by the proposed optimization. We theoretically show that there exists a dual certificate which guarantees exact recovery when the sources are separated by at least 1.68/f c , reducing the gap between the available theoretical guarantee for the source separations and the observed results in the simulations.
16 January 2018 in IEEE Transactions on Instrumentation and Measurement
This paper presents a new filter-based algorithm to estimate the fundamental phasor of fault currents, using the proposed complex frequency filter. The presence of decaying dc component (ddc) in fault currents causes large error in discrete Fourier transform (DFT)-based phasor estimation methods. The proposed filter discriminates the ddc from dc and sinusoidal signals. In this algorithm, first, the ddc is filtered out by the proposed filter. Then, the fundamental phasor can be precisely extracted by applying DFT. Second and fourth order of the complex frequency filter and their design method are presented. To evaluate the performance of the proposed algorithm, several test signals are used. The algorithm is also compared with recent DFT-based and mimic-DFT methods, using four performance indices. The simulation results demonstrate the robustness of the proposed algorithm against harmonics, noise, multiple ddc components, and off-nominal frequency. It also offers faster convergence speed. The proposed complex frequency filter can also be used for the phasor estimation of harmonic components in the presence of ddc with no need to readjust its parameters.
28 February 2024 in IEEE Transactions on Instrumentation and Measurement
High impedance fault (HIF) detection is a problem in distribution power systems protection. Detection of these faults by overcurrent protection relays is difficult or impossible. Therefore, system recovery is postponed, and individuals may be exposed to the risk of electrical shock. This paper defines a family of HIF current-time patterns with different ignition angles. To detect the HIF current, the proposed detection method searches in its family of HIF patterns and finds the pattern that has the highest correlation to the HIF current. Based on the measured correlations, a time-domain algorithm is proposed for the HIF current. If the highest correlation between the family of HIF patterns and the measured current signal is above a given threshold value, then the fault is detected as an HIF. Checked by simulations, the proposed method can correctly detect HIF within one power system cycle.
3 December 2021 in IET Generation, Transmission & Distribution
This paper proposes a high‐speed and accurate method for extracting the arrival times (ATs) of traveling waves (TWs) in the power system that can be used for fault location applications and transmission line protection. The proposed method is based on the expression of the traveling wave as the exponentially damped component superimposed on the sinusoidal wave in a small time window. Also the sine component is removed by using approximation and consecutive differences of the input signal samples (the modal components of three‐phase voltages or currents) from the resulting wave. Due to the fact that the estimation of traveling wave arrival times (TWATs) is done applying basic mathematical operations in the time domain, the proposed method, in addition to the simplicity of implementation, has the appropriate accuracy and speed for applications such as online fault location and protection purposes. In order to evaluate the performance of the proposed approach in fault locating, a 230 kV transmission line is modelled in EMTP/ATP. Then, the fault location under various conditions of faults such as changes in location and type of fault, fault conditions as well as variations in the measurement noise level and sampling frequency are studied using MATLAB.
17 January 2017 in IEEE Transactions on Information Theory
The diversity-multiplexing trade-off (DMT) of half-duplex single-relay networks is computed analytically, where all the channels in the networks are assumed to be quasi-static flat-fading channels with independent Rayleigh distributions. We have computed DMT of dynamic quantize-map-and-forward (DQMF) strategy analytically, which has the optimal DMT for half-duplex single-relay networks with local channel state information. As a result, the optimal listening time of the relay in the DQMF strategy as a function of the source-relay channel realization can also be determined using our solution.