In electrical substations, glass-fibre reinforced polymer (GFRP) insulators provide an alternative to porcelain insulators for better seismic performance. The bonded connection between the composite tube and the metal end fitting is a weak link under earthquake actions, and the failure risk of ultra-high voltage (UHV) substation equipment with GFRP composite insulators can be considerable in places with high seismicity. This study solved the problem by retrofitting and experimentally qualifying the seismic performance of surge arresters made of composite insulators. To ensure safety under a bending moment corresponding to the seismic demand, the bonded sleeve joint between the tube and end fitting was retrofitted by shear stiffeners and higher strength end fitting. A full-scale shaking table test was carried out to verify the performance of the retrofitted surge arrester, and the seismic responses to increasing earthquake actions were analyzed. The specimens in this study were full-scale, had the largest dimensions among substation equipment of the same type, and were subjected to an extremely high earthquake action of 0.5 g; therefore, the seismic testing results produced in this study can serve as an important reference for the industry.
This article introduces an innovative system for enhancing the seismic performance of a structure through facilitating large rotational (rocking) motion to occur without risking overturning. The innovation of this study is in the use of tendons consisting of Nickel‐Titanium (superelastic) alloy connected in series with steel to impose partial restraints to the structure when experiencing rocking motion. Importantly, the large rotational motion is fully recoverable. Existing installations which can be made to rock may also be retrofitted with the device for improving its seismic resistance. The original contributions of the article are the derivation, and experimental validation, of an analytical model for simulating the seismic performance of a system that has been fitted with the restraining device. In a parametric study employing the newly developed modelling techniques, major trends in the seismic response behaviour of the structure have been identified.
1 September 2024 in Journal of Structural Engineering