XUE YAODONG

Dr. XUE YAODONG


Research Focus & Metrics

Academic Career Length

6Years (2021-Present)

(Calculated once Scilit publication data is synced: current year − year of first publication + 1)

Representative Publications

View All Publications
18 October 2022 in Buildings
Verified
Journal Article
Open access
PDF file
SLSheng Li
Sheng Li
YCYongfeng Cheng
Yongfeng Cheng
ZLZhicheng Lu
Zhicheng Lu
Nelson LamNelson Lam
Nelson Lam
XYXUE YAODONG
XUE YAODONG
HWHaibo Wang
Haibo Wang
In electrical substations, glass-fibre reinforced polymer (GFRP) insulators provide an alternative to porcelain insulators for better seismic performance. The bonded connection between the composite tube and the metal end fitting is a weak link under earthquake actions, and the failure risk of ultra-high voltage (UHV) substation equipment with GFRP composite insulators can be considerable in places with high seismicity. This study solved the problem by retrofitting and experimentally qualifying the seismic performance of surge arresters made of composite insulators. To ensure safety under a bending moment corresponding to the seismic demand, the bonded sleeve joint between the tube and end fitting was retrofitted by shear stiffeners and higher strength end fitting. A full-scale shaking table test was carried out to verify the performance of the retrofitted surge arrester, and the seismic responses to increasing earthquake actions were analyzed. The specimens in this study were full-scale, had the largest dimensions among substation equipment of the same type, and were subjected to an extremely high earthquake action of 0.5 g; therefore, the seismic testing results produced in this study can serve as an important reference for the industry.

4 February 2022 in Mechanics of Advanced Materials and Structures
Verified
Journal Article
Closed access
XYXUE YAODONG
XUE YAODONG
YCYongfeng Cheng
Yongfeng Cheng
QLQing Li
Qing Li
KWKai Wang
Kai Wang
WXWenlong Xu
Wenlong Xu
WDWeisheng Du
Weisheng Du
Instability failure of rock masses containing joints has always been a hot topic in rock mechanics. To study the mechanical failure mechanism of rock masses containing internal joint under impact loading, a digital laser dynamic caustic system combined with high-speed photography was used to perform drop hammer impact experiments. The mechanical parameter of dynamic fracture of polymethyl methacrylate (PMMA) beams and physical parameters such as crack extension trajectory and extension velocity were obtained. The extended finite element method was adopted to simulate the propagation process of the internal joint in the PMMA beam, then the von Mises stress distribution and crack extension velocity were obtained. The research results show that: the fracture mode of the three-point bending beam containing internal prefabricated crack is Mode-I; the lower end of the internal crack starts to crack firstly and the initiation toughness shows a tendency to increase and then decrease as the distance between the crack and the specimen boundary ascends; the “unloading stress wave” excited by the prefabricated crack lower end can significantly increase degree of the stress concentration at the crack upper end and promote the cracking. For specimens containing internal crack at different positions, the initiation toughness of the crack upper end increases by 152%, 62%, 88%, 250%, and 176% compared with lower end, respectively. The dynamic failure mechanism of a three-point bending beam containing internal joint has been proposed based on experiment results and numerical simulation. The proposed dynamic failure mechanism facilitates better understanding of failure process of rocks containing joint and for engineering applications related to rock mass fracture.

1 January 2021 in Advances in Civil Engineering
Verified
Journal Article
Open access
PDF file
XYXUE YAODONG
XUE YAODONG
YCYongfeng Cheng
Yongfeng Cheng
ZZZhubing Zhu
Zhubing Zhu
SLSheng Li
Sheng Li
ZLZhenlin Liu
Zhenlin Liu
SZShujun Zhang
Shujun Zhang
In order to consider the influence of nonlinear characteristics of porcelain pillar electrical equipment on the dynamic response under seismic excitation, a theoretical analysis method of nonlinear dynamics was raised to define the nonlinear parameter of the flange connection and establish a dynamic model of porcelain pillar electrical equipment. The theoretical analysis and the test results have a good degree of fitting, which verifies the correctness of the dynamic model and reveals the nonlinear seismic response law of the porcelain pillar equipment. According to the results, both the nonlinear calculation results of the displacement at the top end of the porcelain pillar and the stress at the bottom end of the porcelain pillar are smaller than the results in the linear calculation. The difference between them increases gradually with the increase of seismic excitation. The differences in displacement and stress at a seismic excitation of 0.5 g are 14.58% and 23.25%, respectively. When the nonlinear parameter increases to a certain value, the impact of maximum stress on the bottom of the porcelain pillar is very small and the change is not obvious. The research provides a theoretical reference for the seismic design of pillar electrical equipment.

7 February 2023 in Bulletin of Engineering Geology and the Environment
Verified
Journal Article
Closed access
PDF file
XYXUE YAODONG
XUE YAODONG
LBLiren Ban
Liren Ban
WDWeisheng Du
Weisheng Du
CQChengzhi Qi
Chengzhi Qi
WZWang Zefan
Wang Zefan
TJTianwei Jin
Tianwei Jin

16 September 2022 in Journal of Earthquake Engineering
Verified
Journal Article
Closed access
YCYongfeng Cheng
Yongfeng Cheng
XYXUE YAODONG
XUE YAODONG
WDWeisheng Du
Weisheng Du
ZLZhicheng Lu
Zhicheng Lu
Ultra-high voltage (UHV) transformer has a high seismic vulnerability. The transformers are usually directly connected to the shaking table to conduct an experiment to study its seismic performance, without considering the effect of the foundation soil on the upper equipment. In the present study, the transformer was scaled down based on the dimensional theory. Then, a soil box that can effectively eliminate the boundary effect is designed and a method that can simulate the site category is proposed. Finally, shaking table tests were conducted on rigid foundations and type I site for the scaled-down model, the seismic response of equipment under different site types is obtained. The results imply that under the rigid foundation, the transformer body response is larger with the seismic wave input in the X+Z direction compared to the seismic wave input in the X-direction; as the seismic acceleration increase, the acceleration and strain of bushings gradually ascend, and the response of bushing with Y direction earthquake wave input is significant than that with X direction earthquake wave input. Under type I site condition, with the earthquake excitation increase, the acceleration amplification effect for transformer body caused by the soil–structure interaction decreases gradually; the response of high voltage bushing under earthquake waves is more significant compared with medium and low voltage bushing; with the earthquake excitation increases, the acceleration of high voltage bushing is 1.13 to 1.40 times that of rigid foundation connection, and the strain response is 1.01 to 1.26 times that of rigid foundation connection. The research findings can be applied in the seismic field of UHV transformers to improve the level of seismic design.

14 April 2026 in Buildings
Verified
Journal Article
Open access
PDF file
YZYue Zhang
Yue Zhang
XYXUE YAODONG
XUE YAODONG
ZZZhubing Zhu
Zhubing Zhu
YSYuhan Sun
Yuhan Sun
SLSen Lin
Sen Lin
KWKai Wang
Kai Wang
In earthquake engineering and hydraulic engineering, the dynamic mechanical behavior of cohesive soils is crucial to ensure structural stability. However, most existing dynamic constitutive models fail to adequately account for the influence of strain history, which is essential for accurately predicting soil behavior under seismic loading. This study conducted a series of cyclic single-shear tests on both in situ and disturbed Changsha cohesive soils. Hysteresis curves were obtained under varying shear strain amplitudes to investigate the degradation patterns of the dynamic shear modulus and the evolution of the damping ratio. Furthermore, multi-cycle loading tests under constant strain amplitude were carried out to clarify the correlation between damping ratio, dynamic shear modulus, and the number of loading cycles. A simplified practical dynamic model, applicable to general cohesive soils, is proposed. This model incorporates the effect of strain history and provides a valuable reference for analyzing the dynamic response of soils subjected to earthquake actions.