A reasonable acoustic power formula is vital to precisely evaluate the audible noise (AN) level of ultra-high-voltage (UHV) AC power lines. This study derived a formula by taking several AN measurements under heavy rain conditions, using multiple conductor bundles in a UHV corona cage, and then subjecting these measured values to least squares fitting. The validity of the proposed formula was subsequently verified with statistical data obtained from two long-term stations at Henan and Hubei Province, which are located under the Jindongnan-Nanyang-Jingmen UHV AC transmission lines operating at 1000 kV. The deviation between the prediction and the long-term (L50) value was 0.76 dB for the Henan station and 0.17 dB for the Hubei station. It shows that the acoustic power formula derived in this paper is more accurate than the widely used Bonneville Power Administration formula, in which the corresponding deviations are much larger (3.07 and 2.53 dB).
Humidity is a critical factor in atmospheric corona discharge. Fluid dynamics models have become a common method to explore the detailed corona discharge characteristics in humid air. However, the models require the specification of some key parameters, such as electron swarm parameters and Townsend coefficients, which strongly depend on the electron energy distribution function (EEDF). In this paper, the EEDFs of dry air and water vapor are compared by solving the electron Boltzmann equation using classical the two-term approximation. Moreover, electron drift velocity in dry air and water vapor are compared and validated. Finally, effects of humidity on the electron swarm parameters and Townsend coefficients are also discussed. The results show that the electron drift velocity in dry air and water vapor in this paper is well consistent with the previous experimental results for a wide range. It is concluded that the humidity could increase the electron mobility coefficient and decrease the electron diffusion coefficient in low reduced electric field, which are insensitive to humidity in high reduced electric field. The strength of ionization and attachment reactions are both enhanced by humidity, and the corona onset electric fields increase with the increase in humidity.
4 September 2017 in Journal of Physics D: Applied Physics
A numerical simulation method of negative direct current (DC) corona discharge based on a plasma chemical model is presented, and a coaxial cylindrical gap is adopted. There were 15 particle species and 61 kinds of collision reactions electrons involved, and 22 kinds of reactions between ions are considered in plasma chemical reactions. Based on this method, continuous Trichel pulses are calculated on about a 100 us timescale, and microcosmic physicochemical process of negative DC corona discharge in three different periods is discussed. The obtained results show that the amplitude of Trichel pulses is between 1–2 mA, and that pulse interval is in the order of 10 −5 s. The positive ions produced by avalanche ionization enhanced the electric field near the cathode at the beginning of the pulse, then disappeared from the surface of cathode. The electric field decreases and the pulse ceases to develop. The negative ions produced by attachment slowly move away from the cathode, and the electric field increases gradually until the next pulse begins to develop. The positive and negative ions with the highest density during the corona discharge process are and , respectively.
9 November 2017 in IEEE Transactions on Electromagnetic Compatibility
Radio interference (RI) induced by the corona discharge of alternating current transmission lines is more severe at high altitudes than at low altitudes; hence, RI is a crucial limiting factor in the structural design of transmission lines and environmental impact assessments. To determine RI performance at high altitudes, the State Grid Corporation of China constructed an ultrahigh-voltage (UHV) corona cage in Xining in 2015 at an altitude of 2261 m. In this study, the cage was used to investigate a high number of bundled conductors under heavy rain. An RI excitation function was derived from Xining and the effects of several variables on RI performance were analyzed. In addition, RI altitude corrections were studied by comparing the Xining data with data obtained from a UHV corona cage in Wuhan located at an altitude of 23 m. The RI correction value was verified not to be a constant value but rather one that changed with the surface electric field and bundle size. The correction values obtained in this paper could enable the RI levels of high-voltage alternating current transmission lines at high altitudes to be evaluated more precisely.
1 October 2015 in IET Science, Measurement & Technology
To investigate the effect of altitude on radio interference (RI) of AC power lines, a corona cage test system was used to measure the RI excitation function values of different bundle conductors in different altitude locations, such as Wuhan 23 m, Jingyuan 1408 m, Xining 2261 m, Gonghe 2943 m and Yangbajain 4300 m. Then, the RI curves with different altitudes, bundle numbers and subconductor diameters were obtained. The analysis and comparison show that the actual RI altitude correction values fall in between the range of 1 dB/300 m and 40(1 − σ / σ0 ) when the altitude below 3200 m, which is widely used as Italian correction term and Westinghouse correction term, respectively. Above this altitude, they are not applicable to predict the correction values. In this study, an RI correction term is proposed from the test results, which are fitted well for different altitude regions <4300 m.
The audible noise (AN) induced by corona discharge of AC transmission lines is more severe at high altitudes than at low altitudes; this has become a crucial limiting factor for the structural design of power lines and their environmental impact assessment. To determine the altitude effect and correction of AN level for AC power lines, a corona cage test system was used to measure the acoustic power level of four bundled conductors at five elevations, namely Wuhan (23 m), Tianshui (1100 m), Xining (2261 m), Gonghe (2943 m), and Yangbajain (4300 m). We obtained the AN characteristics for different altitudes, bundle numbers, and subconductor diameters through a statistical analysis of measured data. The analysis and comparison results indicate that the actual AN correction values are slightly less than the Bonneville Power Administration term of 1 dB/300 m at altitudes below 3200 m. Above 3200 m, the difference increases gradually. A correction term 2.85 dB/1000 m is recommended for more accurate evaluation.