The Middle East, including the six Gulf Cooperation Council (GCC) states, is among the world's fastest-growing data center regions. Its live IT capacity, about 1.2 GW in 2025, is forecast to grow by roughly 60% a year, and projects announced across the Middle East and North Africa exceed 14 GW, against about 5 GW expected by 2030. The main GCC hubs face dry-bulb temperatures of about 43-46 • C, wet-bulb temperatures near 31 • C, seawater temperatures above 35 • C in the summer, regular dust storms, and mostly desalinated municipal water. This is the first review to combine climate, deployment, power, cooling, water, and waste-heat data for the region. Cooling with outside air works only in winter, when savings are small, and coastal summer air is too humid to bring indoors. Cooling towers work all year, even on the humid coast, but consume water. Liquid cooling with warm water is the most promising way to avoid both chillers and water use for most of the year, if the servers accept warm water. The Red Sea and Omani coasts, unlike the Persian Gulf, offer cool deep seawater. The region's large district cooling networks, some supplied with treated wastewater, remain largely untapped by data centers. At Gulf prices, evaporative cooling costs less to run than dry cooling, even with desalinated water, whenever dry cooling would raise energy use by more than about 3-9%. The real water constraint is how desalinated water is allocated and delivered at summer peaks, not its price. Data center waste heat has no heating market but could drive cooling or desalination, although desalination driven by data center heat has yet to be demonstrated in the field.