Single-phase inverters with an output LC filter, can generate low distortion output voltages, which are suitable for uninterruptible power supply (UPS) systems. The UPS system provides emergency power in the case of utility power failure, requiring high reliability and clean power. The sensorless control method is actually a soft-sensing technique, that reduces system cost, measurement-related losses, and, especially important for UPS systems, enhances the system reliability. This paper proposes a load current sensorless finite control set model predictive control (FCS-MPC) scheme for a single-phase UPS inverter. A time varying observer is proposed, which offers the accurate estimation for individual components simultaneously in periodic load current signal, without subsequent complex calculations. Compared with another two typical sensorless methods (the low-pass filter and the Kalman filter), the proposed observer-based FCS-MPC strategy has smaller load current estimation error and lower output voltage distortion, under both linear and nonlinear loads. The theoretical analysis is verified through simulation and experiment. A single-phase inverter rapid control prototype (RCP) is set up with the Speedgoat real-time target machine, to confirm the effectiveness of the system.
With the development of power switches and processor performance in recent years, the control frequency of inverters has been significantly improved. However, limited by technology and price, the sensor sampling frequency in large-scale industrial applications is much lower than the inverter control frequency that can be realized. This frequency mismatch limits the performance improvement of the inverter. In this article, the current and voltage at the non-sampling time are reconstructed using the current prediction control principle and the input observer theory, allowing a single-phase inverter to implement multi-sampling rate control with a low sampling frequency and high control frequency. In addition, an improved adaptive controller is designed to solve the effect of incorrect model parameters, which realizes adaptive control when the sampling frequency and control frequency are mismatched. Finally, the effectiveness of the method is verified through a simulation and experiments. The proposed method can solve the problem of high-speed switching for inverters under low-sampling-frequency conditions, improving the inverter’s adaptive performance and robustness.