A small-signal model of photovoltaic (PV) generation connected to weak AC grid is established based on a detailed model of the structure and connection of a PV generation system. An eigenvalue analysis is then employed to study the stability of PV generation for different grid strengths and control parameters in a phase-locked loop (PLL) controller in the voltage source converter. The transfer function of the power control loop in the dq rotation frame is developed to reveal the influence mechanism of PLL gains on the small-signal stability of PV generation. The results can be summarized as follows: ① oscillation phenomena at a frequency of about 5 Hz may occur when the grid strength is low; ② the tuning control parameters of the PLL have a noticeable effect on the damping characteristics of the system, and larger proportional gain can improve the system damping;③ within a frequency range of 4-5 Hz, the PLL controller has positive feedback on the power loop of PV generation. A virtual inductance control strategy is proposed to improve the operational stability of PV generation. Finally, a simulation model of PV generation connected to weak AC grid is built in PSCAD/EMTDC and the simulation results are used to validate the analysis.
13 October 2020 in Journal of Electrical Engineering & Technology
This paper introduces a standalone clamping switched capacitor –based dc transformer (CSCDCT) for the medium-voltage dc power grid. The CSCDCT owns the functions of the dc fault isolation and the on-line redundant design, and hence the power distribution reliability can be guaranteed. It is also shown that the additional advantages of the CSCDCT are the matching regulation of the high-frequency ac voltages and the voltage self-balance of the dc capacitors. The coupling effect of ac voltage amplitudes and dc voltages can be eliminated by the matching regulation and the action of dc voltages will not alter the amplitude of high-frequency ac voltages in CSCDCT, improving the soft-switching performance, efficiency and control stability of the DCT system. Besides, by the self-balance capability, the dc capacitor voltage balancing mechanism is not required for the individual unit although two capacitors are used in each sub-module. This simplify the control system of the CSCDCT. The topology, operating mode, voltage matching modulation, current characteristic, switching performance, and power loss of the CSCDCT are investigated in detail. The correctness of the analysis is validated through the experimental and simulation results.
In this study, a small signal model of paralleled inverters for multiple photovoltaic (PV) generation units (MPGUs) connected to weak grid is developed. Based on the proposed small signal model, eigenvalue analysis is employed to study the stability of MPGUs within different grid strength, different control parameters in each phase‐locked loop (PLL) controller and varying operating points in each PV generation unit. Furthermore, based on the transfer function of the power control loops in dq rotation frame, the coupling mechanism of operating point in each PV unit is revealed. The results show that: with the increasing of output power of PV unit among the PV generation and the decreasing of the grid strength, it may occur oscillation phenomena, the oscillation frequency is about 5 Hz; tuning gains of PLL has noticeable effect on the damping characteristic of the system, and larger PLL gains can improve system damping; each PV unit power control loop is coupled by the point of common coupling voltage, increasing the output power of PV unit, it may reduce the phase margin of the system transfer function and deteriorate the system stability. Theoretical analysis is verified with simulation of MPGUs connected to weak grid.
8 December 2020 in Journal of Electrical Engineering & Technology