Artificial Intelligence (AI) techniques are considered the most advanced approaches for diagnosing faults in power transformers. Dissolved Gas Analysis (DGA) is the conventional approach widely adopted for diagnosing incipient faults in power transformers. The IEC-599 standard Ratio Method is an accurate method that evaluates the DGA. All the classical approaches have limitations because they cannot diagnose all faults accurately. Precisely diagnosing defects in power transformers is a significant challenge due to their extensive quantity and dispersed placement within the power network. To deal with this concern and to improve the reliability and precision of fault diagnosis, different Artificial Intelligence techniques are presented. In this manuscript, an artificial neural network (ANN) is implemented to enhance the accuracy of the Rogers Ratio Method. On the other hand, it should be noted that the complexity of an ANN demands a large amount of storage and computing power. In order to address this issue, an optimization technique is implemented with the objective of maximizing the accuracy and minimizing the architectural complexity of an ANN. All the procedures are simulated using the MATLAB R2023a software. Firstly, the authors choose the most effective classification model by automatically training five classifiers in the Classification Learner app (CLA). After selecting the artificial neural network (ANN) as the sufficient classification model, we trained 30 ANNs with different parameters and determined the 5 models with the best accuracy. We then tested these five ANNs using the Experiment Manager app and ultimately selected the ANN with the best performance. The network structure is determined to consist of three layers, taking into consideration both diagnostic accuracy and computing efficiency. Ultimately, a (100-50-5) layered ANN was selected to optimize its hyperparameters. As a result, following the implementation of the optimization techniques, the suggested ANN exhibited a high level of accuracy, up to 90.7%. The conclusion of the proposed model indicates that the optimization of hyperparameters and the increase in the number of data samples enhance the accuracy while minimizing the complexity of the ANN. The optimized ANN is simulated and tested in MATLAB R2023a—Deep Network Designer, resulting in an accuracy of almost 90%. Moreover, compared to the Rogers Ratio Method, which exhibits an accuracy rate of just 63.3%, this approach successfully addresses the constraints associated with the conventional Rogers Ratio Method. So, the ANN has evolved a supremacy diagnostic method in the realm of power transformer fault diagnosis.
Power transformers are critical assets in complex power grid systems, yet On-Load Tap Changers (OLTCs) account for over 30% of documented outages. This study introduces a Health Index (HI) model for OLTCs that employs a Fuzzy-Logic system to enhance condition-based maintenance (CBM) techniques. This research presents a component-wise, Fuzzy-Logic–based HI evaluation using the Scoring Methodology. The OLTC component is subdivided into six smaller components or contributors. Every contributor is a crucial subsystem whose efficacy is vital to the transformer’s overall reliability. Each contributor is divided into three sub-contributors/values and assessed using a three-tier classification scale (A, B, or C). These values could indicate condition measurements, operational observations, and diagnostic data. Each value is evaluated against reference ranges or boundary values derived from a synthesis of international standards, statistical population studies, and expert knowledge. To verify the precision of the proposed methodology, several defective OLTC cases were evaluated under diverse operational settings. This Fuzzy-Logic (FL) approach seeks to deliver a more accurate and interpretable assessment of OLTC condition than traditional crisp-value methods by integrating expert knowledge, diagnostic metrics, and standards within a structured Fuzzy-Inference framework. The implicit FL model is inherently more attuned to early indicators of deterioration and hidden risk factors that may be underestimated in conventional expert evaluations. Implementation of this intelligent monitoring approach enables early fault diagnosis, extends the transformer’s operational life, and reduces the risk of catastrophic failures and unplanned outages in the electrical power network.