A new control method for a line-commutated converter-based (LCC) high-voltage direct-current (HVDC) system is presented and compared to a conventional strategy. In the proposed method, both the DC voltage and current of an LCC HVDC system are regulated to increase the short-term operating margin of DC power transfer and improve transient responses to DC power references. In particular, an increased operating margin of DC power transfer is achieved via the DC voltage regulation method. To verify the effectiveness of the proposed method, a state space model of an LCC HVDC system is developed considering DC voltage and current references as input variables and analyzed for various values of the DC line inductance and converter controller gains. The state space model can be used for time-efficient analyses of the dynamic characteristics of an LCC HVDC system. Simulation case studies are performed using MATLAB, where the state space model of the Jeju-Haenam HVDC system is implemented as a test case and compared to its comprehensive PSCAD model. The case study results suggest that the proposed method increases the short-term operating margin and speeds up the transient response of the HVDC system. Therefore, it will effectively improve real-time grid frequency regulation.
29 June 2020 in IEEE Transactions on Energy Conversion
A new DC current-voltage droop control method for a hybrid high-voltage direct-current (HVDC) system featuring a voltage-sourced converter (VSC) rectifier and a line-commutated converter (LCC) inverter is presented. The proposed method utilizes DC voltage droop control to reduce the AC voltage fluctuation at the inverter side, to exploit the hybrid HVDC system for connecting offshore wind farms to weak grids without necessitating continuous reactive power compensation facilities. Additionally, an optimal droop coefficient calculation method is proposed to keep the AC voltage constant for wind power fluctuations. To evaluate the stability of the proposed method, a small-signal state-space (SS) model of the target system is derived and the root locus analysis is given. Simulation case studies are performed using an electromagnetic transient model in PSCAD and an SS model in MATLAB. The results demonstrate that a hybrid HVDC system with the proposed method successfully integrates offshore wind energy and weak grids without additional facilities because the AC voltage can be maintained at a near constant during wind fluctuations.
High-voltage direct-current (HVDC) systems for constant or intermittent power delivery have recently been developed further to support grid frequency regulation (GFR). This paper proposes a new control strategy for a line-commutated converter-based (LCC) HVDC system, wherein the dc-link voltage and current are optimally regulated to improve real-time GFR in both rectifier- and inverter-side grids. A dynamic model of an LCC HVDC system is developed using the dc voltage and current as input variables, and is integrated with feedback loops for inertia emulation and droop control. A linear quadratic Gaussian (LQG) controller is also designed for optimal secondary frequency control, while mitigating conflict between the droop controllers of HVDC converters. An eigenvalue analysis is then conducted, focusing on the effects of model parameters and controller gains on the proposed strategy. Simulation case studies are performed using the models of a real HVDC system and a CIGRE benchmark system. The case study results confirm that the proposed strategy enables the HVDC system to improve GFR, in coordination with generators in both-side grids, by exploiting the fast dynamics of HVDC converters. The proposed strategy is also effective under various conditions for the LQG parameters, inertia emulation, and droop control.
We propose frequency and voltage control method for a hybrid high-voltage direct current (HVDC) system for integrating an offshore wind farm into transmission networks. Conventionally, DC voltage level is maintained as constant regardless of the wind velocity and the grid frequency, so AC voltage fluctuates with active power variation in a hybrid HVDC system due to the innate reactive power absorption of inverter side line-commutated converter (LCC). However, in the proposed method, the DC voltage changes according to the wind velocity. Furthermore, DC voltage is simultaneously regulated to participate in frequency control in a communication-free manner. These two characteristics can be achieved by using five droop control methods proposed here. Additionally, by determining droop constants using the proposed determination methods, AC voltage can be maintained as constant during active power fluctuations. Therefore, using the proposed method, an offshore wind farm can be stably connected to mainland transmission networks and successfully used as frequency supporting resources, because voltage characteristics of the AC network are not destabilized. A small-signal state-space (SS) model of the target system was also developed to investigate stability of the proposed control. The utility of the proposed method is demonstrated by case studies using PSCAD and SS models.
6 January 2020 in IEEE Transactions on Power Systems
In this paper, a new control method for a line-commutated converter-based (LCC) high-voltage direct current (HVDC) system to support the frequency and AC voltage was proposed. For coordinated control of the inverter and rectifier, droop-based controllers are adopted for the outer loop of conventional controllers, and DC voltage is used to transfer the frequency information so that communication is not required. A method to determine the droop constants of the proposed controller is presented to emulate the conventional f/P droop characteristic and suppress the AC voltage fluctuations. Furthermore, a small-signal state-space model of the LCC HVDC system with the proposed scheme is derived, and root locus analysis is carried out to evaluate its stability. The effects of the proposed method are verified based on case studies, using the well-known CIGRE BENCHMARK model. The advantages of the proposed method can be summarized as follows: 1) system reliability is enhanced because there is no risk of communication failure during frequency information transfer and 2) voltage stability at the inverter side is enhanced as AC voltage fluctuation during frequency support is minimized.
28 October 2019 in IEEE Transactions on Power Delivery
We present a new reactive power control method for hybrid high-voltage direct-current (HVDC) systems that features a line-commutated converter-based (LCC) rectifier and a voltage-sourced converter-based (VSC) inverter. Our principal objective is to regulate the reactive power of the LCC rectifier side via co-operative control of the DC voltage and switched shunt devices (SSDs) such as capacitors and reactors. To achieve these objectives, we used three operative modes: reactive power, voltage, and power factor control. For each mode, we show how to determine the DC reference voltage. Also, to maintain the voltage within operational bounds and enhance the range over which reactive power is controllable, our method features the cooperation of SSDs. Furthermore, we show how to determine the required SSD capacities. MATLAB and PSCAD simulations confirmed that our method improves reactive power controllability at the LCC rectifier side of a hybrid HVDC system.