Terahertz (THz) spectroscopy is a promising technique for the stand-off detection and characterization of hidden objects. The THz band is particularly well suited firstly because THz radiation penetrates many dielectrics like clothes and secondly because many potentially hazardous substances have characteristic signatures in the THz spectral region. In order to utilize the full potential of THz radiation for detecting possible hazards and recognizing characteristic signatures, disturbing influences must be accounted for. We have performed experiments and simulations in order to investigate the limits of terahertz stand-off detection. A special emphasis is paid on humidity in ambient air and properties of the sample like surface roughness, alignment and interfaces. Water vapor absorption strongly affects the THz spectra. Since the absorption lines are strong and narrow, the calculation must be precise. We have checked various models well-known in meteorology covering the infrared and the microwave region of the electromagnetic spectrum. By extending the models into the THz region, an accurate description of the measured spectral absorption is achieved. In our studies transmission spectra for different substances were tested. In a reflection scheme metallized sandpaper of various grit sizes was used to determine the influences of different surface properties. Further measurements were performed for different tilt angles to analyze the influence of the surface roughness. We are currently creating a look-up table to show which parts of the THz spectrum can be used for THz stand-off detection.
The increasing use of renewable energy sources in place of conventional generation units is leading to a reduction in onshore inertia and to the development of offshore wind park grids connected by multiple high-voltage direct current (HVDC) connections to the onshore alternating current (AC) grid. For AC-side meshed offshore grids with voltage-source converter (VSC) and diode rectifier unit (DRU) HVDC connections towards onshore grids, this study focuses on the energetic feasibility of synthetic inertia (SI) and primary control reserve (PCR) contributions triggered locally at the onshore converters of both connection types. To this end, the obstacles preventing contributions for VSC HVDC connections and the mechanisms allowing contributions for DRU HVDC connections are identified first. Based on these findings, the article proposes an enhancement of the offshore HVDC converter controls that is continuously active and allows locally triggered onshore contributions at all onshore HVDC converters of both connection types without using communication and requiring only minimal system knowledge. Additional simulations confirm that, although the enhancement is continuously active, the operational performance of the offshore HVDC converter controls for normal offshore grid operation and its robustness against offshore AC-side faults are not affected.