The worldwide demand on data storage continues to increase and both the number and the size of data centers are expanding rapidly. Energy efficiency is an important factor to consider in data centers since the total energy consumption is huge. The servers must be cooled and the performance of the cooling system depends on the flow field of the air. Computational Fluid Dynamics (CFD) can provide detailed information about the airflow in both existing data centers and proposed data center configurations before they are built. However, the simulations must be carried out with quality and trust. The k– model is the most common choice to model the turbulent airflow in data centers. The aim of this study is to examine the performance of more advanced turbulence models, not previously investigated for CFD modeling of data centers. The considered turbulence models are the k– model, the Reynolds Stress Model (RSM) and Detached Eddy Simulations (DES). The commercial code ANSYS CFX 16.0 is used to perform the simulations and experimental values are used for validation. It is clarified that the flow field for the different turbulence models deviate at locations that are not in the close proximity of the main components in the data center. The k– model fails to predict low velocity regions. RSM and DES produce very similar results and, based on the solution times, it is recommended to use RSM to model the turbulent airflow data centers.
In data centers, efficient cooling systems are required to both keep the energy consumption as low as possible and to fulfill the temperature requirements. The aim of this work is to numerically investigate the effects of using partial aisle containment between the server racks for hard and raised floor configurations. The computational fluid dynamics (CFD) software ANSYS CFX was used together with the Reynolds stress turbulence model to perform the simulations. Velocity measurements in a server room were used for validation. Boundary conditions and the load of each rack were also retrieved from the experimental facility, implying an uneven load between the racks. A combination of the performance metrics Rack Cooling Index (RCI), Return Temperature Index (RTI) and Capture Index (CI) were used to evaluate the performance of the cooling systems for two supply flow rates at a 100% and 50% of operating condition. Based on the combination of performance metrics, the airflow management was improved in the raised floor configurations. With the supply flow rate set to operating conditions, the RCI was 100% for both raised floor and hard floor setups. The top- or side-cover fully prevented recirculation for the raised floor configuration, while it reduced the recirculation for the hard floor configuration. However, the RTI was low, close to 40% in the hard floor case, indicating poor energy efficiency. With the supply flow rate decreasing with 50%, the RTI increased to above 80%. Recirculation of hot air was indicated for all the containments when the supply rate was 50%, but the values of RCI still indicated an acceptable performance of the cooling system.
In this paper hard floor and raised floor cooling of servers are numerically compared. Both time-averaged and transient distributions of velocity and temperature fields are investigated with the use of computational fluid dynamics. The geometry and boundary conditions are based on Module 2 of the RISE SICS North facility located in Lulea, Sweden. Results show that for hard floor configurations, it is important to ensure that the hot air does not enter the server inlets on the return to the cooler unit. For raised floor configurations, the interplay between inlet air velocity and server fan speed should instead be considered. Flow fields further indicate that flow direction control of the outlet air in hard floor configurations and inlet air in raised floor configurations can be applied to improve the energy efficiency of the server room. Regarding transient effects, the hard floor configuration show overall larger velocity oscillations while corresponding temperature variations are comparatively small.