1 March 2018 in Journal of Electronic Packaging
Verified
Journal Article
Closed access
PDF file
SKSadegh Khalili
Sadegh Khalili
MTMohammad I. Tradat
Mohammad I. Tradat
KNKourosh Nemati
Kourosh Nemati
MSMark Seymour
Mark Seymour
Bahgat G SammakiaBahgat G Sammakia
Bahgat G Sammakia
In raised floor data centers, tiles with high open area ratio or complex understructure are used to fulfill the demand of today's high-density computing. Using more open tiles reduces the pressure drop across the raised floor with the potential advantages of increased airflow and lower noise. However, it introduces the disadvantage of increased nonuniformity of airflow distribution. In addition, there are various tile designs available on the market with different opening shapes or understructures. Furthermore, a physical separation of cold and hot aisles (containment) has been introduced to minimize the mixing of cold and hot air. In this study, three types of floor tiles with different open area, opening geometry, and understructure are considered. Experimentally validated detail models of tiles were implemented in computational fluid dynamics (CFD) simulations to address the impact of tile design on the cooling of information technology (IT) equipment in both open and enclosed aisle configurations. Also, impacts of under-cabinet leakage on the IT equipment inlet temperature in the provisioned and under-provisioned scenarios are studied. In addition, a predictive equation for the critical under-provisioning point that can lead to a no-flow condition in IT equipment with weaker airflow systems is presented. Finally, the impact of tile design on thermal performance in a partially enclosed aisle with entrance doors is studied and discussed.

8 March 2022 in Journal of Electronic Packaging
Verified
Journal Article
Closed access
PDF file
MTMohammad I. Tradat
Mohammad I. Tradat
YMYaman “Mohammad Ali” Manaserh
Yaman “Mohammad Ali” Manaserh
AGAhmad Gharaibeh
Ahmad Gharaibeh
BSBahgat G. Sammakia
Bahgat G. Sammakia
DHDave Hall
Dave Hall
MSMark Seymour
Mark Seymour
An increasingly common power saving practice in data center thermal management is to swap out air cooling unit blower fans with electronically commutated plug fans, Although, both are centrifugal blowers. The blade design changes: forward versus backward curved with peak static efficiencies of 60% and 75%, respectively, which results in operation power savings. The side effects of which are not fully understood. Therefore, it has become necessary to develop an overall understanding of backward curved blowers and compare the resulting flow, pressure, and temperature fields with forwarding curved ones in which the induced fields are characterized, compared, and visualized in a reference data center which may aid data center planning and operation when making the decisions of which computer room air handler (CRAH) technology to be used. In this study, experimental and numerical characterization of backward curved blowers is introduced. Then, a physics-based computational fluid dynamics model is built using the 6sigmaroom tool to predict/simulate the measured fields. Five different scenarios were applied at the room level for the experimental characterization of the cooling units and another two scenarios were applied for comparison and illustration of the interaction between different CRAH technologies. Four scenarios were used to characterize a CRAH with backward curved blowers, during which a CRAH with forwarding curved was powered off. An alternate arrangement was examined to quantify the effect of possible flow constraints on the backward curved blower's performance. Then parametric and sensitivity of the baseline modeling are investigated and considered. Different operating conditions are applied at the room level for experimental characterization, comparison, and illustration of the interaction between different CRAH technologies. The measured data is plotted and compared with the computational fluid dynamics (CFD) model assessment to visualize the fields of interest. The results show that the fields are highly dependent on CRAH technology. The tile to CRAH airflow ratios for the flow constraints of scenarios 1, 2, 3, and 4 are 85.5%, 83.9%, 61%, and 59%, respectively. The corresponding leakage ratios are 14.5%, 16%, 38.9%, and 41%, respectively. Furthermore, the validated CFD model was used to investigate and compare the airflow pattern and plenum pressure distribution. Lastly, it is notable that a potential side effect of backward curved technology is the creation of an airflow dead zone.

24 May 2024 in Journal of Electronic Packaging
Verified
Journal Article
Closed access
PDF file
AGAhmad R. Gharaibeh
Ahmad R. Gharaibeh
QSQusai Soud
Qusai Soud
YMYaman Manaserh
Yaman Manaserh
MTMohammad I. Tradat
Mohammad I. Tradat
Bahgat G SammakiaBahgat G Sammakia
Bahgat G Sammakia
The variety of new electronic packaging technologies has grown significantly over the last 20 years as a result of market demands for higher device performance at lower costs and in less space. Those demands have pushed for heterogeneous packaging, where computer chips with different stack heights are closely packed, creating nonuniform heat flux and temperature and additional challenges for thermal management. Without implementing an appropriate thermal management strategy for heterogeneous packages, large temperature gradients can be observed within the package, which would increase the thermal stresses on the chip and raise reliability issues. To mimic this real-life scenario of such packaging, an experimental setup was designed and built. The design of the new experimental setup consists of four identical 1.2 cm × 1.2 cm ceramic heaters, each of which is connected to a separate power supply and can reach a heat flux of 140 W/cm2. Accordingly, this mock package is capable of delivering different power levels to mimic different multicore microprocessor conditions. To give the heater the ability to move precisely in the x-, y-, and z-directions, each heater is mounted to an XYZ linear stage. Deionized water (DI) was used as the working fluid, and a pin-fin heat sink was used to run the initial steady-state tests on the experimental rig. The tests showed how different flow rates at a constant fluid temperature and input power affect the temperatures of the heaters and the thermohydraulic performance of the heat sink. In addition, a three-dimensional numerical model has been developed and validated with experimental data in terms of heat sink pressure drop and the temperatures of the heaters.

8 August 2022 in Journal of Electronic Packaging
Verified
Journal Article
Closed access
PDF file
VRVahideh Radmard
Vahideh Radmard
AGAhmad R. Gharaibeh
Ahmad R. Gharaibeh
MTMohammad I. Tradat
Mohammad I. Tradat
CHCong Hiep Hoang
Cong Hiep Hoang
YMYaman Yaseen Manaserh
Yaman Yaseen Manaserh
Bahgat G SammakiaBahgat G Sammakia
Bahgat G Sammakia
More than ever before, data centers must deploy robust thermal solutions to adequately host the high-density and high-performance computing that is in high demand. The newer generation of central processing units (CPUs) and graphics processing units (GPUs) has substantially higher thermal power densities than previous generations. In recent years, more data centers rely on liquid cooling for the high-heat processors inside the servers and air cooling for the remaining low-heat information technology equipment. This hybrid cooling approach creates a smaller and more efficient data center. The deployment of direct-to-chip cold plate liquid cooling is one of the mainstream approaches to providing concentrated cooling to targeted processors. In this study, a processor-level experimental setup was developed to evaluate the cooling performance of a novel computer numerical control (CNC) machined nickel-plated impinging cold plate on a 1 in. × 1 in. mock heater that represents a functional processing unit. The pressure drop and thermal resistance performance curves of the electroless nickel-plated cold plate are compared to those of a pure copper cold plate. A temperature uniformity analysis is done using compuational fluid dynamics and compared to the actual test data. Finally, the CNC machined pure copper one is compared to other reported cold plates to demonstrate its superiority of the design with respect to the cooling performance.

23 February 2022 in Journal of Electronic Packaging
Verified
Journal Article
Closed access
PDF file
GMGhazal Mohsenian
Ghazal Mohsenian
CHCong Hiep Hoang
Cong Hiep Hoang
KNKourosh Nemati
Kourosh Nemati
HAHussam Alissa
Hussam Alissa
MTMohammad I. Tradat
Mohammad I. Tradat
Bahgat G SammakiaBahgat G Sammakia
Bahgat G Sammakia
The practice of commissioning data centers (DCs) is necessary to confirm the compliance of the cooling system to the information technology equipment (ITE) load (design capacity). In a typical DC, there are different types of ITE, each having its physical characteristics. Considering these geometrical and internal differences among ITE, it is infeasible to use the actual ITE as a self-simulator. Hence, a separate device called load bank is employed for that purpose. Load banks create a dummy thermal load to analyze, test, and stress the cooling infrastructure. Available commercial load banks do not accurately replicate a server's airflow patterns and transient heat signatures which are governed by thermal inertia, energy dissipation, flow resistance, and fan system behavior. In this study, a novel prototype of the server called server simulator was designed and built with different components to be used as a server mockup. The server simulator accurately captured air resistance, heat dissipation, and the functionality of actual server behavior. Experimental data showed up to 93% improvement in ITE passive and active flow curves using the designed server simulator compared to the commercial load bank. Furthermore, the experimental results demonstrated a below 5% discrepancy on the critical back pressure and free delivery point between the actual ITE and the designed server simulator. In addition, experimental data indicated that the developed server simulator improved the actual ITE thermal mass by 27% compared to the commercial load bank.

16 July 2021
Verified
Preprint
Open access
CHCong Hiep Hoang
Cong Hiep Hoang
MTMohammad I. Tradat
Mohammad I. Tradat
BRBharath Ramakrisnan
Bharath Ramakrisnan
SRSrikanth Rangarajan
Srikanth Rangarajan
YHYaser Hadad
Yaser Hadad
Scott N SchiffresScott N Schiffres
Scott N Schiffres
The miniaturization of microelectronic devices and an increasing demand for clock speed result in high heat flux systems. By adopting direct liquid cooling, the high heat flux and high-power demands can be met, while the reliability of the electronic devices is greatly improved. In this paper, thermo-hydraulic performance of a commercial hybrid micro-channel/slot-jet heat sink with