As a class of devices used in sound detection, electromagnetic acoustic transducers (EMATs) have been widely used in the field of nondestructive testing (NDT) owing to their advantages such as contact-free operation, wide applicability, and high performance. However, their low energy-conversion efficiency is the main drawback that limits usage in industrial testing. In this work, we report the effect of different parameters of the point-focusing shear-horizontal EMAT (PFSH-EMAT) on the signal intensity of the receiving transducer. The impact factors of the focusing transducer are as follows: number of magnets in a row m, fan-shaped periodic permanent magnet (FPPM) remanence magnetization Br, coil width w, coil winding number n, aperture angle h, focal length lF, lift-off distance hl, excitation current frequency fc, and current amplitude Ic. To improve the analysis efficiency, an L32(49) orthogonal table is used to investigate the nine different factors at four levels, which can be calculated through finite element simulations. The effect of each factor on the signal intensity is obtained by range analysis, and the optimal combination of these impact factors can be achieved by reasonable level selection. Through range analysis, the influence degree of each factor is obtained, and the parameter combination is optimized by analyzing the test results to improve the PFSHEMAT’s performance. The experimental results show that the optimized PFSH-EMAT is 170% more efficient than the average of the top-three signal intensities in the orthogonal test, which proves the effectiveness of the proposed optimization method.
1 March 2015 in IET Generation, Transmission & Distribution
The electric field and ion current distribution on the ground level and corona losses are the important factors for designing high‐voltage direct current (HVDC) transmission lines. This study presents a new finite‐difference‐based flux tracing (FDFT) method for analysing the ionised field. The differential equations are discretised using the finite‐difference method and the non‐linear algebraic equations are constructed. For the bipolar field, a systematic technique to set up the initial values is well established by estimating the average values of space charge density. The issues of the finite‐difference scheme, the normalisation and the selection of mesh points are elaborately discussed to have a better convergence. The boundary conditions of the ionised field equations can be enforced directly, whose benefit is that the iterative process to satisfy the boundary conditions can be completely avoided. The numerical examples show that the results obtained in this study agree well with the ones published in other literatures. The FDFT could be applied for more complicated line configuration with unequal corona‐onset electric fields and ion mobilities of opposite polarities.
30 October 2017 in IEEE Transactions on Power Delivery
Building HVDC and HVAC transmission lines in the same corridor or even on the same tower is an attractive way to extend electricity transport capacity where getting the new right of way is difficult. The resulting hybrid lines produce a new corona performance, such as ground-level hybrid electric field and ion current density, which are quite different from those of pure AC or DC lines. In this paper, inherent space-time pattern and characteristics of the information propagation in Lagrangian description are presented for the ion transport problem, i.e., the ion density at a certain point has a direct relationship with its drift time. Based on this, the theoretical explanation is provided for the decoupling algorithm, by which the ground-level DC component can be solved with the AC conductors assumed to be at zero potential and vice versa. The simulation results show that the sinusoidal AC field has negligible influence on the DC ion drift time from conductor surface to ground while stationary electric field generated by the grounded AC lines has a dominant effect. Therefore AC energization has rather low impact on ground-level quantities and the simplification of grounded AC conductors is quite reasonable.
10 January 2018 in IET Generation, Transmission & Distribution
The ion‐flow environment is an important corona design factor of HVDC transmission lines. The space charges generated by corona form a typical convection‐dominated ion‐flow field. For this special transport phenomenon, however, standard Galerkin FEM always presents serious deficiencies. In this study, a new approach is used to solve ion‐flow field based on Petrov–Galerkin method derived from the theory of fluid computation. A high‐order stabilisation technique is used to overcome the non‐physical oscillations in the presence of highly convective effects. This algorithm is equivalent to the proper modification of weight function according to the direction and magnitude of local drift velocity. It reflects the characteristic of information propagation in flow problem. The establishment procedure of weak form and matrix gives a further explanation on the deficiency of Galerkin method. Moreover, to guarantee convergence of the iteration for this fully‐coupled non‐linear problem, a relaxation method is introduced in the iterative loop. Calculations with the Petrov–Galerkin least square method are in good agreement with analytical solution and experiment values of ground‐level values and corona losses. Results show that the proposed stabilisation technique is able to preclude the numerical spurious oscillation and has a higher‐order accuracy than the fully‐upwind treatment.
The information of earth structure is curial for designing the grounding system and evaluating thetransmission line parameters. In order to obtain the earth structure using the measured data, an efficientalgorithm for the parameter estimation of a horizontally multilayered soil by using a novel integration methodis proposed. In the proposed algorithm, an adaptive iteration process will terminate till the predefined errorreaches the requirement, where the earth parameters, such as the layer depth, layer resistivity, and layer number,are adjusted accordingly with the help of the Levenberg-Marquardt algorithm. In each iteration, the key is toevaluate the apparent resistivity and its partial derivatives with respect to soil parameters, which are expressedin the form of general Sommerfeld integral (GSI). In this paper, the GSI is divided into two parts. The first partwith an infinite upper limit is integrated along a novel complex integration path instead of the conventionalreal axis path, which makes the evaluation of the GSI highly efficient due to the fast damping property of thetransformed kernel. The second part with the finite integral interval is calculated using the cubic splinetechnique to have a semi-analytic expression, which can avoid evaluating the oscillatory kernel. In comparisonwith the results in the published literatures, numerical examples show that the proposed soil parametersestimation approach can reach good accuracy, and is robust and efficient. The reason is simple as the GSIs arecalculated by using the well-designed and sophisticated approach. With extensive numerical experiments, theproposed algorithm is believed to be a capable and applicable candidate in engineering to invert the informationof the earth structure.
To reduce the computational time for solving multiconductor transmission lines (MTL), an iterative solution with a spatial decomposition and the second-order finite-difference time domain (FDTD) is presented. The coupling effects among the MTL are equivalent by a set of distributed voltage and current sources, which decouples the MTL. The voltages and the currents along the lines are evaluated by the second-order FDTD at each iteration step, and the equivalent distributed sources are updated accordingly. The solution of MTL is obtained when convergence is reached. The proposed approach is validated by the numerical examples. The major advantage of the proposed approach, by nature, is an inherent parallel algorithm, which will reduce the computational time, especially for the MTL system with nonlinear devices.