30 December 2019 in Energies
Verified
Journal Article
Open access
PDF file
BQBin Qian
Bin Qian
TYTao Yu
Tao Yu
HBHaiquan Bi
Haiquan Bi
BLBo Lei
Bo Lei
In recent years, the energy performance of public buildings has attracted substantial attention due to the significant energy-saving potential. As a semi-open high-space building, the high-speed railway station is obviously different from other public buildings and even traditional stations in terms of energy consumption and internal environment. This paper investigates the current energy consumption situation and environmental quality of 15 high-speed railway passenger stations in China. Results show that the energy consumption of the high-speed railway station is between 117–470 kWh/(m2·a). The energy consumption of the station is related to the area and the passenger flow. The energy use of the station using district heating is higher than that of the station without district heating in the same region. The higher glazing ratio induces good natural lighting in the station, but the uniformity of the lighting in the station is not good. The acceptable temperature range of passengers in winter is larger than that in summer. The average air change rate of the high-speed railway station is 3.2 h−1 in winter and 1.8 h−1 in summer, which is the main reason of high energy consumption of the HVAC (Heating Ventilation Air Conditioning) system in this kind of building.