This paper addresses the critical challenge of detecting, separating, and classifying partial discharges in substations. It proposes two solutions: the first involves developing a signal conditioning system to reduce the sampling requirements for PD detection and increase the signal-to-noise ratio. The second approach uses machine learning techniques to separate and classify PD based on features extracted from the conditioned signal. Three clustering algorithms (K-means, Gaussian Mixture Model (GMM), and Mean-shift) and the Support Vector Machine (SVM) method were used for signal separation and classification. The proposed system effectively reduced high-frequency components up to 50 MHz, improved the signal-to-noise ratio, and effectively separated different sources of partial discharges without losing relevant information. An accuracy of up to 93% was achieved in classifying the partial discharge sources. The successful implementation of the signal conditioning system and the machine learning-based signal separation approach opens avenues for more economical, scalable, and reliable PD monitoring systems.
This work presents a methodology for the generation and classification of phase-resolved partial discharge (PRPD) patterns based on the use of a printed UHF monopole antenna and signal conditioning circuit to reduce hardware requirements. For this purpose, the envelope detection technique was applied. In addition, test objects such as a hydrogenerator bar, dielectric discs with internal cavities in an oil cell, a potential transformer and tip–tip electrodes immersed in oil were used to generate partial discharge (PD) signals. To detect and classify partial discharges, the standard IEC 60270 (2000) method was used as a reference. After the acquisition of conditioned UHF signals, a digital signal filtering threshold technique was used, and peaks of partial discharge envelope pulses were extracted. Feature selection techniques were used to classify the discharges and choose the best features to train machine learning algorithms, such as multilayer perceptron, support vector machine and decision tree algorithms. Accuracies greater than 84% were met, revealing the classification potential of the methodology proposed in this work.
This work presents a methodology for the generation and classification of phase resolved partial discharges (PRPD) patterns based on the use of a printed UHF monopole antenna and signal con-ditioning circuit to reduce hardware requirements. For this purpose, envelope detection technique was applied. In addition, test objects such as a hydrogenerator bar, dielectric disks with internal cavities in an oil cell, potential transformer, and tip-tip electrodes immersed in oil were used to generate partial discharge (PD) signals. To detect and classify partial discharges, the standard IEC 60270 (2000) method was used as reference. After acquisition of conditioned UHF signals, digital signal filtering threshold technique was used, and peaks of partial discharges envelopes pulses were extracted. Feature selection techniques were used to classify the discharges and choose the best features to train machine learning algorithms, such as multilayer perceptron, support vector ma-chine and decision tree. Accuracies greater than 84% were met, revealing the classification potential of the methodology proposed in this work.
Partial discharge localization is a crucial step in monitoring high-voltage equipment. Over time, due to data acquisition limitations, signal strength has become a key driver of methods of localization. In the literature, the variety of testing conditions makes it challenging to identify the factors influencing localization accuracy clearly. Furthermore, there is a lack of research using real equipment as a source of partial discharge. This paper presents a meta-analysis of data from monitoring systems used for radiometric localization of partial discharge sources, employing algorithms based on the time difference in arrival and received signal strength indicator. The obtained results show that the data exhibited errors with a high standard deviation, indicating that many studies are conducted under significantly different conditions. The first method is more sensitive to noise and the sampling rate, while the second is influenced by the source type and the number of sensors. Moreover, laboratory experiments performed with a potential transformer exhibiting partial discharge suggest that signal propagation in real equipment might not be omnidirectional, which can affect accuracy. Consequently, results based on controlled sources, where source directionality and obstacles have a significant impact on performance, do not accurately reflect real-world conditions. The obtained results indicate that the more realistic the source, the higher the errors will be, due to the lower uniformity in signal propagation.