Faced with increasingly bulk power transfer by voltage source converter (VSC)-based HVDC systems, the stability of VSC stations is of interest. Two widely adopted control schemes, that is, to control the VSC as a current source (e.g., the current vector control) or to control the VSC as a voltage source (e.g., the virtual synchronous machine-based control), are analyzed near the power limit. Bottlenecks of the first control scheme are pointed out and a novel quasi-steady-state method to seek the corresponding critical short-circuit ratio is proposed. Distinctive impacts of the short-circuit ratio on the second control scheme are also analyzed. According to the analysis and relevant comparison, supplementary compensators are proposed to provide extra damping for the two control schemes so that they are able to cope with a wider range of grid strengths. The analytical results and enhancement strategies are validated by time-domain simulations. Suggestions on dividing strong and weak systems with respect to VSCs are finally put forward and which control scheme is preferred under different conditions is discussed.
17 August 2016 in IEEE Transactions on Power Systems
This paper proposes an improved analytical model for the study of steady-state performance of droop-controlled VSC-MTDC systems. When power disturbances occur, such as those imposed by normal changes in power settings and converter outages, the powers of the converters with droop control may hit their limits and hence such converters no longer contribute to power sharing, which should be paid special attention when analyzing the impacts of power disturbances on the performance of multi-terminal HVDC (MTDC) systems. Based on the bisection algorithm and superposition principle, the proposed analytical model provides an easy way to estimate the results of power distributions, dc voltage deviations, and power loss variations of the MTDC system taking converter outage and converter overload into account. Simulations of a modified New England 39-bus system incorporating a four-terminal MTDC system are carried out for validating the proposed analytical model.
In this paper, the DC short-circuit fault and corresponding clearance solutions of modular multilevel converter-based high-voltage direct current (MMC-HVDC) systems are analyzed in detail. Firstly, the analytical expressions of DC fault currents before and after blocking the MMC are derived based on the operation circuits. Before blocking the MMC, the sub-module (SM) capacitor discharge current is the dominant component of the DC fault current. It will reach the blocking threshold value in several milliseconds. After blocking the MMC, the SM capacitor is no longer discharged. Therefore, the fault current from the AC system becomes the dominant component. Meanwhile, three DC fault clearance solutions and the corresponding characteristics are discussed in detail, including tripping AC circuit breaker, adopting the full-bridge MMC and employing the DC circuit breaker. A simulation model of the MMC-HVDC is realized in PSCAD/EMTDC and the results of the proposed analytical expressions are compared with those of the simulation. The results show that the analytical DC fault currents coincide well with the simulation results.
A method for electromechanical modeling of line commutated converter (LCC)-modular multilevel converter (MMC)-based hybrid multi-terminal High Voltage Direct Current Transmission (HVDC) systems for large-scale power system transient stability study is proposed. Firstly, the general idea of modeling the LCC-MMC hybrid multi-terminal HVDC system is presented, then the AC-side and DC-side models of the LCC/MMC are established. Different from the conventional first-order DC-side model of the MMC, an improved second-order DC-side model of the MMC is established. Besides considering the firing angle limit of the LCC, a sequential power flow algorithm is proposed for the initialization of LCC-MMC hybrid multi-terminal HVDC system. Lastly, simulations of small scale and large scale power systems embedded with a three-terminal LCC-MMC hybrid HVDC system are performed on the electromechanical simulation platform PSS/E. It is demonstrated that if the firing angle limit is not considered, the accuracy of the power flow solutions will be greatly affected. Steady state calculation and dynamic simulation show that the developed LCC-MMC hybrid MTDC model is accurate enough for electromechanical transient stability studies of large-scale AC/DC system.
This paper determines the minimum short circuit ratio (SCR) requirement for a modular multilevel converter based high-voltage direct current (MMC-HVDC) transmission systems. Firstly, a simplified model of MMC is introduced; the MMC is represented by its AC and DC side equivalent circuit. Next, by linearizing the MMC subsystem and the DC network subsystem, the deduction of the small-signal models of MMC subsystem, the small-signal model of the DC network and MMC-HVDC are carried out successively. Thirdly, the procedure for determining the minimum SCR requirement of MMC-HVDC is described. Finally, case studies are performed on a two-terminal MMC-HVDC system under four typical control schemes. The results show that the restraint factors for the rectifier MMC is predominantly the voltage safety limit constraint, and the restraint factors for the inverter MMC are mainly the phase locked loop (PLL) or the outer reactive power controller. It is suggested that the minimum SCR requirement for the sending and the receiving systems should be 2.0 and 1.5 in the planning stage.
This paper aims to discover the general steady-state operation characteristics, as well as improving the dynamic performance, of the modular multilevel converter (MMC)-based unified power flow controller (UPFC). To achieve this, first, we established a detailed power flow model for MMC-based UPFC containing each critical part and made qualitative and graphical analyses combining 2-dimensional operation planes and 3-dimensional spatial curve surfaces comprehensively to derive general power flow principles and offer necessary references for regulating UPFC. Furthermore, to achieve better performance, we designed a feedforward control strategy for the shunt and series converters of UPFC, both comprising two feedforward control blocks with the introduction of necessary compensating branches, and analyzed the performance in complex and time domain, respectively. The proposed power flow principles and control strategies were validated by a (power systems computer aided design) PSCAD model of 220 kV double-end system; the results reveal the MMC-based UPFC can realize the power flow principles and improve the control speed, stability, and precision of the power flow regulations under various conditions.