Ensuring proper indoor air quality in high-rise apartment buildings is a crucial challenge, particularly when upgrading ventilation systems during deep energy renovation of existing buildings. This study evaluates the condition of existing ventilation systems and assesses the performance, cost, and energy efficiency of different mechanical ventilation solutions with heat recovery, including centralized and decentralized balanced ventilation with heat recovery, single-room ventilation units, and mechanical extract ventilation with heat pump heat recovery or without heat recovery. An onsite survey revealed significant deficiencies in existing ventilation systems, such as airtight window installations without dedicated fresh air valves, misaligned and decayed exhaust shafts, and inadequate extract airflow in kitchens and bathrooms. SWOT analyses for each system highlighted their strengths, weaknesses, opportunities, and threats, providing valuable insights for decision-makers. The results indicate that while centralized and decentralized mechanical ventilation with heat recovery enhances energy efficiency and indoor air quality in high-rise multifamily apartment buildings, challenges such as high installation costs, maintenance complexity, and architectural constraints must be addressed. Heat recovery with exhaust air heat pumps is a viable alternative for high-rise apartment buildings when more efficient options are not feasible.
Optimal placement of outdoor air intakes and exhaust outlets is a source control measure to avoid the degradation of air quality at the air intakes. Re-entrainment is an occasional air pollution instance that happens if pollutants in the exhaust air stream, after being discharged to outdoors, are transferred back to outdoor air intake location due to unfavorable meteorological conditions and inadequate positioning of the air intakes and exhaust outlets. In engineering practice, it is impractical to always conduct detailed dispersion modeling due to the complexity of airflow phenomena in the urban environments, and therefore, engineers rely on prescriptive design guidelines or simplified empirical models published in technical literature and regulation documents. Commonly, the design guidelines to avoid the re-entrainment phenomenon are for buildings with rooftop exhaust stacks, but the exhaust outlets might also be situated on the building façade. The objective of this paper is to overview the existing design guidelines for the placement of horizontal air intakes and exhaust outlets. Technical engineering literature, including international standards, codes, and guidebooks is reviewed to extract both qualitative and quantitative design guidelines relevant to the placement of air intakes and exhausts on an external wall.
The purpose of the study was to experimentally test the performance of four types of wall-mounted mechanical ventilation exhaust air outlet devices. A full-scale mock-up of a segment of an external wall with an exhaust air outlet was constructed. The tested exhaust air devices include a gravity louver, fixed-blade louver, louver plate, and exhaust nozzle. The performance assessment included two types of experiments over the exhaust airflow rate range of 25–94 l/s at isothermal conditions with no influencing wind: (i) the particle tracer method with smoke to visualize the exhaust air jets from the outlets, and (ii) the tracer gas method to measure the dilution of CO2 concentration in the exhaust air jet. Furthermore, the aerodynamic performance was comparatively evaluated in terms of pressure drop and exhaust air face velocity at the outlet. The qualitative comparison of airflow patterns by smoke visualization showed notable differences between the tested device types. Concentration decrease evaluation indicated that the exhaust air pollutants are more efficiently transported away from the building wall by exhaust outlets that discharge at 0–45 degrees downwards from the horizontal plane. Discharge angles 60–90 degrees downwards produced a wall-attached jet and the pollutant tracer concentration remained relatively high in the vicinity of the wall.