This study proposes a new air treatment system that integrates dehumidification, cooling, and water recovery using a Horizontal Air–Ground Heat Exchanger (HAGHE) combined with Peltier cells. The airflow generated by a fan flows through an HAGHE until it meets a septum on which Peltier cells are placed, and then separates into two distinct streams that lap the two surfaces of the Peltier cells: one stream passes through the cold surfaces, undergoing both sensible and latent cooling with dehumidification; the other stream passes through the hot surfaces, increasing its temperature. The two treated air streams may then pass through a mixing chamber, where they are combined in the appropriate proportions to achieve the desired air supply conditions and ensure thermal comfort in the indoor environment. A Computational Fluid Dynamics (CFD) analysis was carried out to simulate the thermal interaction between the HAGHE and the surrounding soil. The simulation focused on a system installed under the subtropical climate conditions of Nairobi, Africa. The simulation results demonstrate that the HAGHE system is capable of reducing the air temperature by several degrees under typical summer conditions, with enhanced performance observed when the soil is moist. Condensation phenomena were triggered when the relative humidity of the inlet air exceeded 60%, contributing additional cooling through latent heat extraction. The proposed HAGHE–Peltier system can be easily powered by renewable energy sources and configured for stand-alone operation, making it particularly suitable for off-grid applications.
This work experimentally investigates the behavior of a new indoor air conditioning system based on the application of Peltier cells in a Horizontal Air–Ground Heat Exchanger (HAGHE). To this end, a laboratory-scale prototype focusing exclusively on the terminal section of the system was developed and tested under controlled conditions. A series of configurations was tested, each representing an evolution of the previous one. The results highlight the strong dependence of system performance on airflow velocity, applied voltage, and heat dissipation effectiveness, demonstrating both the potential and the critical limitations of the proposed configurations. The most promising results were obtained in the advanced (fourth and fifth) configurations, yielding average temperature increases of approximately +1.9 °C on the hot flow and decreases ranging from −1.0 °C to −1.7 °C on the cold flow at moderate total voltages (40–50 V) and higher airflow velocities (0.5–0.6 m/s). In line with the principles of the circular economy, the prototype was constructed using recycled materials, including plastic pipes and Peltier cells recovered from discarded devices.