Modular multilevel converter (MMC) based high voltage direct current (HVDC) transmission system is one of the important development trends of DC power grid. After fault isolation, the traditional reclosing method of MMC-HVDC system is directly reclosing DC circuit breaker (DCCB). Once the fault point still exists, DCCB will be tripped again. This method will make the DC system suffer from the secondary strike of fault in a short time, and seriously endanger the service life of DCCB. In order to overcome the drawbacks of the traditional reclosing schemes, this paper proposes a novel adaptive reclosing scheme based on pulse injection from parallel energy absorption module. When dc fault current is interrupted by DCCB, the fault energy stored in current-limiting reactors (CLR) and dc lines is transferred to energy absorption module automatically. By switching on IGBTs embedded in absorption module for a short time, a voltage pulse is injected directly into the faulty line without interference from CLR. Then the nature of fault is identified and the fault distance can also be calculated in the case of permanent faults. The simulation results verify the effectiveness of the proposed scheme.
The impedance-based criteria are well known to assess the stability of DC systems by impedance measurement method. However, these criteria apply to the DC systems with the precondition of the interconnected converters or subsystems having no right-half-plane (RHP) poles, which is hard to guarantee and verify in a complicated DC distribution power system (DPS) with multiple parallel connected converters. To solve it, this paper proposes a combined bus port impedance based stability criterion for the DC DPS, where the number of RHP poles of the combined bus port impedance are proven zero definitely. Thus, the DC DPS is judged stable if and only if the trajectory of the proposed combined bus port impedance does not encircle the origin (0, 0), which is easily and feasibly determined by measuring port impedance of individual converter, without acquiring its inner information. Specifically, the oscillation frequency can be observed intuitively from the Bode plot of the combined bus port impedance. Three experimental systems are provided to validate the proposed stability criterion.
17 January 2025 in IEEE Transactions on Industrial Electronics
Insufficient reactive voltage support and power angle divergence are critical issues threatening the stable operation of virtual synchronous generators (VSG) under faults. However, existing research lacks comprehensive transient control methods considering both voltage and transient angle stability and fails to explore transient enhancement strategies after fault current limiting. In this paper, a fault circuit model for VSG considering current limiting is established, revealing the impact mechanisms of different Q-U controller on voltage transient support in phasor diagrams. Subsequently, the influence of fault current limiting on transient angle stability is discussed. Based on this, a transient control method for VSG considering both voltage support and transient angle stability is proposed. This method utilizes virtual capacitance and virtual resistance to modify Q-U and P-f controllers, respectively, to achieve reactive voltage support and transient angle suppression under faults. Furthermore, the application of the proposed method under fault current limiting is discussed, and the idea of fault current redistribution is proposed to enhance voltage support strength and reduce fault instability risk. Finally, hardware-in-loop experiments validate the correctness and effectiveness of the theoretical analysis and proposed.
1 July 2013 in Journal of Electrical Engineering & Technology
Lightning disturbance may be misjudged as dc fault by the primary protection in the flexible high voltage dc (HVDC) grid. To solve this problem, an auxiliary fault identification strategy based on convolutional neural network with branch structures (BR-CNN) is proposed in this paper. In the proposed scheme, the voltage and current characteristic matrix is constructed as the input matrix of BR-CNN model and the output categories include positive pole-to-ground (PTG) fault and lightning disturbance. Voltage and current branches are constructed to extract high-level local features of input data layer by layer, and main branch is designed to realize the comprehensive utilization of voltage and current information. Through autonomous learning of the model, the nonlinear mapping relationship between input and output is constructed. The method only uses the single-terminal quantities, and can be used as an auxiliary criterion to improve the reliability of the primary protection. The test results verify the effectiveness of the method, and the recognition accuracy is better than the traditional classification models.