With the rapid development of renewable energy, multi-terminal flexible DC grids composed of modular multilevel converters have been widely used in power systems. To ensure the safe and stable operation of a DC grid, this paper proposes a DC line protection scheme for MMC-based DC grids using AC/DC transient information. In the proposed scheme, the difference between the transient voltage root mean square ratios (DTVR) on both sides of the current-limiting inductor of DC lines is used to identify the DC line fault, and the instantaneous zero sequence voltage (IZSV) of the AC side of the converter station is used to discriminate the faulted poles. According to the theoretical analysis result, a fault criterion setting method suitable for faulted pole discrimination is proposed. The proposed scheme is based on local information and tested in a PSCAD/EMTDC model of a four-terminal MMC-based DC grid. The simulation results show that the scheme can fast and accurately identify faults.
In order to improve the simulation speed of the AC/DC hybrid grid, the inductance/capacitance (L/C) switch model for line-commutated converter of high-voltage direct current (LCC-HVDC) is presented in this study. The time domain modeling method is used to analyze the circuit of L/C switch model for the six-pulse system in LCC-HVDC in a switching period. A parameter setting method of L/C switch model is proposed considering the transient response, the steady state performance, switching losses and simulation error of the switch. The inductance/capacitance (L/C) switch model for LCC-HVDC has the advantage of keeping the admittance matrix unchanged regardless of the change of switching state, which improves the simulation efficiency. Finally, the validity of the parameter setting method is verified. Compared with the test results of PSCAD/EMTDC, the accuracy of the proposed LCC-HVDC simulation model is proved. The model is suitable for real-time or offline simulation of AC/DC hybrid grid.