Thermal comfort, indoor air quality (IAQ), and energy use are closely related, even though these have different aspects with respect to building performance. We analyzed thermal comfort and IAQ using real-time multiple environmental data, which include indoor air temperature, relative humidity, carbon dioxide (CO2), and particulate matter (e.g., PM10 and PM2.5), as well as electricity use from an energy recovery ventilation (ERV) system for a childcare center. Thermal comfort frequency and time-series analyses were conducted in detail to thoroughly observe real-time thermal comfort and IAQ conditions with and without ERV operation, and to identify energy savings opportunities during occupied and unoccupied hours. The results show that the highest CO2 and PM10 concentrations were reduced by 51.4% and 29.5%, respectively, during the occupied hours when the ERV system was operating. However, it was also identified that comfort frequencies occurred during unoccupied hours and discomfort frequencies during occupied hours. By analyzing and communicating the three different types of real-time monitoring data, it is concluded that the ERV system should be controlled by considering not only IAQ (e.g., CO2 and PM2.5) but also thermal comfort and energy use to enhance indoor environmental quality and save energy based on real-time multiple monitoring data.
Change-point regression models are often used to develop building energy baselines that can be used to predict energy use and determine energy savings during a given performance period. However, the reliability of building energy baselines can depend on how well the change-point model fits the data measured during the baseline period. This research proposes the use of segmented linear regression models with one or two change points for automatically driving best-fit building energy baseline models, along with an algorithm using a data-driven grid search to find the optimal change point(s) within a given data boundary for the proposed models. The algorithm was programmed and tested with actual measured data (e.g., daily gas and electricity use) for case-study buildings. Graphical and statistical analysis was also performed to validate its reliability within acceptable deviations of an overall coefficient of variation of the root mean squared error (i.e., CV(RMSE)) of 1%, as compared to the results derived from the ASHRAE Inverse Model Toolkit (IMT) that was developed as a public domain program to manually derive the change-point model with user specified parameters. Consequently, it is expected that the algorithm can be applied for automatically deriving best-fit building energy baseline models with optimal change point(s) from measured data.