This study offers a modular isolated grid-connected DC/DC medium-voltage DC aggregation converter to support offshore full DC wind farms’ need for lightweight and highly efficient power aggregation and transmission. The converter can simultaneously have a smaller transformer size and lower switching frequency during operation through the dual-voltage stabilization three-loop control strategy and phase-shift modulation strategy, which greatly reduces the space occupied by the converter and lowers the switching loss, Additionally, the use of a two-level structure at a lower switching frequency has lower loss, which effectively reduces the cost of the power device compared with the commonly used three-level converter. The input series output series connection between the converter sub-modules effectively lowers the voltage stress on each power switching device and facilitates expansion into a multi-module structure, expanding its application in high-voltage and large-capacity environments. This study analyzes the two working modes of the DC/DC converter and its control approach, in addition to providing a detailed introduction to the application scenarios of this converter. Ultimately, the efficacy and practicability of the suggested topology and control scheme are confirmed by simulations and experiments.
In response to an actual super-synchronous oscillation event in an offshore wind farm, this paper proposes a full-topology real-time simulation (FTRT) scheme based on a self-developed universal link library execution device. The technical challenges of FTRT are systematically analyzed, and a complete modeling and implementation methodology is established. Using this scheme, a hardware-in-the-loop real-time simulation platform incorporating the same type of field controller is built, and the 70 Hz voltage oscillation is accurately reproduced. The analysis reveals that the submarine-cable-based transmission network possesses an inherent resonance point in the super-synchronous frequency band. The system stability boundary is then evaluated by comparing the phase–frequency characteristics of the grid-side and wind-farm impedances. Finally, oscillation suppression measures, including controller parameter unification, impedance reshaping, and SVG (Static Var Generator) deployment, are proposed and verified. The adopted FTRT technology overcomes the accuracy limitations of conventional offline simulations and simplified mechanism analyses, and the results can provide reliable, direct engineering decision support for the planning, design, and operation of offshore wind farms.
Large-scale wind-farm clusters are characterized by intense power fluctuations, various turbine types and time-varying reactive power margins, along with conflicting goals of voltage security and network loss reduction. To address these issues, this paper proposes a hierarchical coordinated reactive power optimization strategy based on an Environment-Aware Particle Swarm Optimization (EAPSO) algorithm. In this study, “environment-aware” specifically refers to operating-condition awareness, including low-load degree, spatial power dispersion, and output imbalance degree of wind turbines. A three-layer framework consisting of cluster level, wind-farm level and unit level is established to coordinate wind-farm reactive power commands, SVG outputs, transformer tap positions, and turbine-level reactive power allocation. A comprehensive disturbance index is constructed from the low-load degree, spatial power dispersion, and output imbalance degree and is then mapped to the initialization strategy, learning factors, and mutation operation of EAPSO. A 24 h offline simulation is conducted using historical operating profiles of a practical large-scale wind-farm cluster in South China. The results show that the proposed strategy reduces the average absolute PCC voltage deviation from 0.013331 p.u. before optimization to 0.004120 p.u. it achieves an average network-loss reduction rate of 3.55%. Compared with Method 1, the transformer tap operation times decrease from 139 to 92, and the cumulative SVG reactive output decreases from 1077.32 Mvar to 208.39 Mvar.
Grid-following converters are prone to transient synchronization instability during grid faults, which may lead to the disconnection of renewable energy devices and threaten the security and stability of power systems. To address this issue, this paper first establishes a second-order nonlinear reduced-order model centered on phase-locked loop dynamics and constructs an energy function to analyze the instability mechanism, revealing the decisive role of equivalent damping in the energy dissipation process. On this basis, an adaptive damping stabilization control strategy based on q-axis voltage feedback is proposed. By introducing the amplitude of the q-axis voltage into the feedback loop to reshape the damping path, the strategy can adaptively adjust the damping according to the fault severity. This control strategy significantly enhances the synchronization stability of grid-following converters: it suppresses oscillations and achieves fault ride-through during transient instability, while limiting the divergence of the power angle during static instability to buy time for fault clearing. Finally, hardware-in-the-loop experiments validate the effectiveness of the proposed strategy.