Data quality issues exist in practical phasor measurement units (PMUs) due to communication errors or signal interferences. As a result, the performances of existing data-driven disturbance classification methods can be significantly affected. In this article, a fast disturbance classification method that is robust to PMU data quality issues is proposed. The impacts of bad PMU measurements on disturbance classification are investigated by analyzing the feature distributions of deep learning methods. A new feature extraction scheme that uses the univariate temporal convolutional denoising autoencoder (UTCN-DAE) is proposed. It allows encoding and decoding univariate disturbance data through a temporal convolutional network to capture the temporal feature representation and is robust to bad data. Based on the features of the frequency and voltage measurements encoded by the UTCN-DAE, a two-stream enhanced network, i.e., the multivariable temporal convolutional denoising network is proposed to achieve optimal feature extraction of multivariate time series by feature fusion. The classification is performed using a multilayered deep neural network and Softmax classifier. Extensive results obtained on the IEEE 39-bus system as well as a large-scale power system in China with field PMU measurements show that the proposed method achieves the highest classification accuracy and computational efficiency as compared to other deep learning algorithms.
Accurate and rapid identification of distribution system fault causes is essential for power system reliability enhancement. Manual fault cause identification requires extensive human resources that leads to extended power outage time. To this end, this paper proposes a dual-channel convolutional neural network (DC-CNN)-based method for distribution system fault cause identification using realistic data from waveform measurement units. The fault mechanism and waveform characteristics of different fault causes are investigated by analyzing large amounts of field waveform data. The short-time Fourier transform (STFT) is advocated to extract the frequency-domain features, which are used together with the time-domain data for constructing the time-frequency feature images. This leads to improved feature extraction via the proposed DC-CNN-enabled multimodal information fusion. A fully connected layer with a maxout unit (FCM layer) is constructed to enhance the mapping ability of high-level features and improve classification accuracy. Extensive test results using field data demonstrate the superiority of the proposed method over other methods.
27 January 2021 in IEEE Transactions on Power Delivery
With the increasing development of renewable energy and high-voltage direct current (HVDC) transmission technology, the integration of power electronics-interfaced components has caused sub-/super-synchronous inter-harmonics into power signals, yielding the subsynchronous oscillations (SSOs). Online monitoring and identification of SSOs are crucial to the secure and stable operation of power systems. This paper proposes a data driven SSOs identification method using realistic phasor measurement unit (PMU) data. Three features are extracted via the analysis of a large number of historical PMU data, which can reflect the SSO features and the interference level. An SSOs identification method is proposed through a multiple-support vector machine (SVM) model. It allows us to adaptively select the proper classifier among the multiple-SVM models according to the interference level estimated by the extracted features. This significantly improves the identification accuracy under both low and high interference inputs of a practical power grid. An automatic update function based on incremental learning is also developed to enhance the model performance when the SSO data are subject to new features. Experimental results using field-measured PMU data validate the advantages of the proposed method over other alternatives.
Phasor measurement units (PMUs) are one of the most effective devices for measuring power system dynamics, and it is critically important that they have good performance. This paper proposes a high-accuracy synchrophasor estimation algorithm and builds a PMU calibrator to offer reference values for PMU test and calibration in the laboratory. Based on a general signal-fitting model, a nonlinear-fitting-based phasor and frequency estimation algorithm using an iterative solution are proposed. A rate-of-change-of-frequency (ROCOF) estimation method using the filter spectrum characteristic of a least-squares method is proposed to improve ROCOF measurement accuracy under dynamic conditions. For PMU laboratory tests, an interference suppression method and a post-processing method for step tests are presented. Then, the selected hardware for the PMU calibrator is tested, and its influence on phasor measurement is analyzed. Simulations and experiments verify that the accuracy of the calibrator is at least 30 times better than the requirements in PMU compliance standards of both IEEE and China, indicating that it can be used for PMU testing and calibration. In addition, the calibrator is also verified that it can offer references with high accuracy under combined tests, since the proposed algorithm is based on one general signal-fitting model.
8 March 2021 in IEEE Transactions on Power Systems
Accurate and fast event identification in power systems is critical for taking timely controls to avoid instability. In this paper, a synchrophasor measurement-based fast and robust event identification method is proposed considering different penetration levels of renewable energy. A difference Teager-Kaiser energy operator (dTKEO)-based algorithm is first proposed to improve multiple-events detection accuracy. Then, feature extractions via the integrated additive angular margin (AAM) loss and the long short-term memory (LSTM) network are developed. This allows us to deal with intra-class similarity and inter-class variance of events when high penetration renewable energy occurs. With the extracted features, a multi-stage weighted summing (MSWS) loss-based criterion is developed for adaptive data window determination and fast event pre-classification. Finally, the re-identification model based on feature similarity is established to identify unknown events, a challenge for existing machine learning algorithms. Simulation results on the IEEE 39-bus, Kundur 2-area, and an actual large-scale power grid system are used to demonstrate the advantages of the proposed method over others.
18 February 2022 in IEEE Transactions on Instrumentation and Measurement
The dynamic characteristics of power systems are becoming increasingly complex with the growing application of power electronics equipment. A high level of real-time monitoring is now required to provide a data basis for system stability and safety control. Therefore, flexible and accurate sensor technology is crucial. In this paper, a non-contact current sensing method is proposed using tunnel magnetoresistance (TMR) technology. Based on the introduction of TMR chip characteristics, the sensing law of a TMR chip surrounding a current-carrying wire is revealed. An arrangement of four TMR chips is then proposed to reflect the magnetic field intensity around a current-carrying wire. A TMR chip array-based non-contact current sensing technique is presented for use as a real set-and-use current sensing method. The convenience of the proposed method is superior to traditional current sensors because the wire does not need to be surrounded by a magnetic ring or coil. A method for location detection is presented to avoid iterating for every sample, which significantly reduces the computation burden. Simulations are then carried out to demonstrate the effectiveness of the proposed method. A current sensor prototype based on a printed circuit board (PCB) is developed, and its practicality is proven by experiments. Test results show that the prototype can meet the requirements of phasor measurement unit (PMU) standards, indicating that the proposed current sensing method is practical and can be applied in M-class and P-class PMUs for current sensing.