Recently, the converters controlled by droop controller with phase-locked loop (PLL) were observed in islanded ac microgrids. However, only state-space-based approach was applied to investigate the stability of this converter in the previous works. Compared with state-space-based approach, characteristic equation approach has plenty of advantages, such as convenient stability margin analysis (Phase Margin, Gain Margin, and so on) and simply stability criterion (Routh Criterion). Thus, a novel small-signal modeling approach based on characteristic equation for converter-dominated ac microgrids is proposed to assess the system low-frequency stability in this paper. Firstly, considering zero-order holder (ZOH) and time delay, the smallsignal characteristic equation of this converter is presented by Padé approximation and dynamic phasor model. Furthermore, the implementation and parameter design of the converters are studied under the practical considerations. Compared with the existing characteristic equation methods, the proposed approach can be verified that the performance is significantly improved. Eventually, simulations and experimental results are presented, indicating that the proposed approach can assess the system lowfrequency stability conveniently and accurately.
14 July 2022 in IEEE Transactions on Automation Science and Engineering
In this paper, the problem of secondary voltage restoration in an islanded microgrid (MG) is considered, in which the actuator of the distributed generators (DGs) may coexist with partial loss of effectiveness (PLOE) fault and bias fault. For each DG, an adaptive event-triggered fault-tolerant (ETFT) control protocol is designed to compensate for the effects of actuator faults in the DGs, thereby restoring the voltage to the reference value. The dependent event triggering mechanism saves the processor’s computational resources. A desirable feature of the protocol proposed in this paper is that the control protocol relies only on relative information between neighboring DG’s, independent of global information about the network graph, fault boundaries, and network scale. It means that the protocol is implemented in a fully distributed framework. The protocol fully applies to the common ETFT consensus control problem of linear multiagent systems (MASs) with actuator faults. Furthermore, comprehensive theoretical arguments for consensus stability and analysis of Zeno behavior ensure the approach’s feasibility. The simulation results verify the effectiveness of the algorithm. Note to Practitioners—This paper aims to propose a fully ETFT control protocol for secondary voltage restoration of an islanded MG. The control protocol consists of a linear term and a nonlinear time that compensates for the multiplicative and additive fault of the actuator. Moreover, DGs’ communication structure and global fault boundaries may be unknown in practice. Hence, adaptive coupling gains that depend only on the sampled relative information of DGs are introduced to estimate the controller gain, thus avoiding global information. A feasible strategy is provided for industrial applications.