Power conversion systems (PCSs) connect dc energy sources to the grid, but background grid-voltage disturbances can degrade grid-current quality. This paper presents a unified derivation and implementation-oriented assessment of proportional grid-voltage feedforward in the abc, αβ, and dq reference frames for an LCL-filtered three-level PCS. The derived disturbance transfer function retains the feedforward term, and attenuation is quantified at the fundamental and selected harmonics. Tests cover gain tuning and voltage harmonics, 10% voltage unbalance, 49–51 Hz operation, SCRs from 10 to 2, ±20% LCL-parameter variation, a 25–50 kW reference ramp, common-mode voltage, and a sixth-harmonic resonant benchmark. With Kff = 0.6, grid-current THD falls from 10.65% to 7.19% in the strong-grid harmonic test; the resonant benchmark reaches 7.05%. At SCR = 3, retuned resonant control gives 20.33% THD versus 11.68% for proportional feedforward, while transferring the strong-grid resonant gain gives 123.02%. The delay-inclusive loop model retains positive stability margins, whereas the switching-model results reveal that the benefit of a fixed feedforward gain is condition-dependent and may diminish or reverse under clean-grid, frequency-deviation, parameter-variation, and weak-grid conditions. Archived 100 kVA waveforms verify stable implementation in all three reference frames. The results clarify the operating conditions under which proportional feedforward is effective, together with its digital implementation requirements and limitations.
The power conversion system (PCS) serves as the core device for power transfer between energy storage systems and the grid, effectively dispatching electricity generated by intermittent sources like renewable energy to match load demands. Conventional grid‐connected PCS architectures typically employ PI regulators for closed‐loop control of the power outer‐loop and current inner‐loop. However, this approach cannot effectively suppress disturbances caused by parameter command variations and grid condition changes. Consequently, traditional PCS systems exhibit degraded quality in grid‐connected output current during power command transients or sudden changes in grid voltage amplitude and frequency. To address these issues, this paper proposes a dual‐loop control method for PCS based on the Uncertainty and Disturbance Estimator (UDE). The dual‐loop parameters of the UDE control are systematically designed. Simulation and experimental results verify that the proposed control method significantly enhances the disturbance rejection capability of the PCS. The experimental results show that the response time of the PCS using the UDE controller can be reduced by more than 50% compared with that using the PI controller.