In this review, the condensation HTCs (heat transfer coefficients) and pressure drop characteristics of some major low-global-warming-potential (GWP) refrigerants alternative to R-134a such as R-1234ze(E), R-1234ze(Z), R-1234yf, R-513A, and R-450A are reviewed. The thermofluids’ characteristics inside/outside a tube, minichannel, microfin tube, and plate heat exchanger are examined. In addition, several other refrigerants attributed to low GWP are also included in the present review. The experimental/numerical/simulation results’ analysis reveals that condensation HTCs and pressure drop characteristics depend on several parameters such as thermodynamics and transport properties of the working fluid, mass flux of the refrigerants, heat flux, saturation temperature, vapor quality, flow patterns, flow conditions, orientation of the condensing geometry, and condensation geometry (shape, size, and smooth/enhanced).
In the present experimental study, nucleate pool boiling heat transfer measurements of two high-flux tubes (sample A and sample B) were conducted at atmospheric pressure with HFE-7200 as the working fluid. Both high-flux tubes were made from a sintered Cu-Ni (high-flux) alloy powder. The porous high-flux surface was coated inside the test tube and it is tested within the heat flux ranging from 2.6 to 86 kW/m2. The major difference between sample A and sample B was the coating thickness, where sample B (0.6 mm) was much larger than that of sample A (0.07 mm). Both tubes showed about three times enhancement in heat transfer coefficient (HTC) when compared to plain tube. Even though sample B contained a higher HTC than sample A, it also revealed a faster level-off phenomenon regarding the HTC vs. wall superheat. The major parameter which characterizes the boiling performance of high-flux tube was the ratio of coating thickness to pore diameter which also yielded different trends upon HTC vs. wall superheat amid sample A and B. It was found that the porous based Nishikawa correlation can well predict the performance of sample A but not sample B. This is because the ratio of coating thickness to pore diameter is far outside the applicable range of the Nishikawa correlation. Hence, a modified Nishikawa correlation is proposed. The predicted capability of the proposed modified Nishikawa correlation against sample A and sample for HTC was within ±28% deviation. The standard mean deviation of the Nishikawa correlation with experimental data for sample A and sample B was 0.302 (12.48%) and 5.64 (73%), respectively.
In this study, the heat transfer performance of high-viscosity polyol ester (POE) oil POEA-220 (220 cSt) with low-GWP (global warming potential) refrigerant R-1234ze(E) on enhanced GEWA-B5H tube was investigated at saturation temperatures of 10 °C, 0 °C, and −6 °C. The mass fraction of oil varied from 0.25% to 10%, and all the nucleate pool boiling data were measured at heat fluxes ranging from 10 kW/m2 to 90 kW/m2. The experimental results showed that the heat transfer performance of the R-1234ze(E)/POEA-220 mixtures were superior to the R-1234ze(E)/POEA-68 mixtures. At saturation temperatures of 0 °C and −6 °C, even a 10% mass fraction of the POEA-220 oil showed an enhancement in the HTC (heat transfer coefficient) compared to the pure refrigerant in the moderate heat flux range. On the other hand, for the R-1234ze(E)/POEA-68 mixtures, a 5% mass fraction of oil showed no enhancement in the HTC compared to pure refrigerant at the same saturation temperature. Moreover, at low saturation temperatures (0 °C and −6 °C), the enhancement in the HTC decreased with increasing mass fraction of low-viscosity oil POEA-68, whereas high-viscosity oil POEA-220 showed the highest enhancement in the HTC for a 5% mass fraction of oil at −6 °C saturation temperature compared to the pure refrigerant. The results indicate that for nucleate boiling, the effect of oil viscosity on heat transfer performance is negligible if it contains comparatively high thermal conductivity and low surface tension. In addition, the effect of surface aging on heat transfer performance for the GEAW-B5H tube with pure refrigerant was also reported.
This study used Computational Fluid Dynamics (CFD) to simulate and analyze the working fluid in magnetic centrifugal refrigerant compressors using R-134a to mixed refrigerant: R-513A and HFO (Hydrofluoroolefins) Hydrofluoroolefin refrigerant: R-1234yf, and the impact on integrated part-load performance, Integrated Part Load Value (IPLV) and internal flow field. This study used a single-stage 280 USRT maglev centrifugal refrigerant compressor as a simulation model. Three different refrigerants were used: R-134a, R-513A, and R-1234yf, as presented in the National Institute of Standards and Technology (NIST) real gas database. The refrigerant was used to set the IPLV working conditions and change the compressor speed and mass flow rate to simulate the compressor’s characteristic curve after replacing the refrigerant. The compressor working conditions were the fixed refrigeration cycle condensation and evaporation following the same capacity standards. This study used the CFD software by Ansys software company to simulate the flow field. The k-omega turbulence software was used to model the turbulence. The results show that the maglev centrifugal refrigerant compressor efficiency dropped significantly when the refrigerant was directly replaced. Based on R-134a, the full load efficiency of R-1234yf dropped 13.21%, the full load efficiency of R-513A dropped 9.97%, and the partial load efficiency was similar to R-134a.
The present investigation conducts a comparative analysis of the nucleate pool boiling heat transfer performance of two dielectric fluids, a low-GWP hydrofluoroolefin-based fluid (commercially known as Opteon™ SF33, referred to hereafter as SF33) and a perfluoropolyether-based fluid with a high GWP (commercially known as GaldenR HT55, referred to hereafter as HT55) under atmospheric pressure conditions. Pool boiling experiments and visual observations were performed to assess essential performance parameters, such as critical heat flux, heat transfer coefficient, and boiling dynamics. SF33 exhibits enhanced heat transfer performance, achieving markedly higher heat transfer coefficient values at all the heat flux levels and attaining superior critical heat flux relative to HT55. The results show that SF33 provides a consistently higher heat transfer coefficient, reaching approximately 12 W/m2·K at maximum heat flux, compared to only 6 W/m2·K for HT55, representing nearly a 100% improvement. The visual observations indicated that reduced surface tension and increased latent heat of vaporization of SF33 facilitate more frequent bubble nucleation and smaller bubble departure, thereby enhancing its boiling performance. Properties of SF33 render it a superior candidate for high-performance cooling systems in data centers and power electronics. The study concludes that SF33 is a more efficient and adaptable fluid for next-generation cooling systems, providing superior heat dissipation and energy efficiency relative to HT55.